background image

10

    S&C Instruction Sheet 1042-511 

Installation

IntelliTeam II System 

Setup

Follow these steps to create an IntelliTeam II Automatic Restoration System:

STEP 1. 

Create a layout of the source(s), switches, and line segments that will include teams. 
Use a system map or similar diagram showing source and switch locations.

STEP 2. 

Plan the communication system. For more information, see the manufacturer 
documentation for the communication system.

STEP 3. 

Identify and name the team(s). Form teams by including all automated switches that 
border each line segment. Assign each team a name, up to 16 characters long. Also, 
assign team designations for “Team 1” to “Team 8,” as needed on the 

Setup>Team X

 

screens. Teams that share a team member must have different designations.

STEP 4. 

Assign a DNP/RTU address for each team member. Each team member requires a 
unique DNP/RTU address. Enter this information on the 

Setup>Team

 screen.

STEP 5. 

Determine the switch/position number for each team member. Each team member 
is associated with a switch/position number, for example, “Sw1” for a single overhead 
switch. Pad-mounted switchgear may have more than two switches, and two 
switches can constitute a team. For example, Team 1 could include switches 1 and 
2, and Team 2 could include switches 2 and 3 in the same pad-mounted gear. Enter 
this information on the 

Setup>Team

 screen.

STEP 6. 

Note the normally 

Open/Closed

 state for each team member. Enter this information 

on the 

Setup>Team

 screen. 

STEP 7.   

Create a layout of the source(s), switches, and line segments that includes the teams.

Every switch should have its sensors facing the normal source of the team.
There are six types of functionality for team members. See Table 1.

Table 1. Functionality Types for Team Members

Functionality

Description

Closed Switches

Source/Sub

Use this value when the normally closed source switch is the 
first team member after the source/substation or is an S&C 
IntelliTeam™ Interface Module on the source breaker relay.

Source

Use this value for one closed switch in the team through 
which the line segment receives power, when the circuit is in 
its normal configuration.

Load/Tie

A team may have zero, one, or multiple closed switches through 
which loads on other line segments receive power. Use this 
value when the switch, when closed, could be used to restore 
power to the line segment indirectly from an alternate source.

Load

A team may have zero, one, or multiple closed switches through 
which loads on other line segments receive power. Use this 
value when the switch would not be involved when restoring 
power to the line segment because the other line segments 
have no alternate sources.

Open Switches

Tie/Sub

Use this value when the tie switch is the first team member 
after the substation/source.

Tie

Use this value for zero, one, or multiple open switches in the 
team that restore power to the line segment directly from an 
alternate source when closed.

Содержание 5800 Series

Страница 1: ...2 Special Warranty Provision 2 Safety Information Understanding Safety Alert Messages 4 Following Safety Instructions 4 Replacement Instructions and Labels 4 Installation Applicable Software 5 Planni...

Страница 2: ...ns of sale as set forth in Price Sheets 150 and 181 applies to the S C 6800 Series Automatic Switch Control except that the first paragraph of the said warranty is replaced by the following 1 General...

Страница 3: ...s applicable instruction sheets This warranty does not apply to major components not of S C manufacture such as batteries and communication devices However S C will assign to the immediate purchaser o...

Страница 4: ...if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not f...

Страница 5: ...trol or in the switch control itself during certain switchgear wiring or grounding system failures or due to a problem with the switch control itself For this reason access to switch controls should b...

Страница 6: ...ion see the About Fault Detection Switch Control Setup Point 6 in Instruction Sheet 1042 531 S C 5800 Series Automatic Switch Controls With IntelliTeam II Automatic Restoration System Setup When confi...

Страница 7: ...that will be part of the IntelliTeam II system Plan the communication system for peer to peer transmission and for data interchange with the SCADA master station if one is used Name the teams 16 chara...

Страница 8: ...nication hardware installation instructions Start IntelliLink software and establish communication between the team member and your computer setup instructions Use IntelliLink software to enter all se...

Страница 9: ...IntelliLink Remote Setup Software Is this the last team that needs to be checked Is each team where this control is a member ready for transfer Make sure all switches are in their normal configuration...

Страница 10: ...STEP 6 NotethenormallyOpen Closedstateforeachteammember Enterthisinformation on the Setup Team screen STEP 7 Createalayoutofthesource s switches andlinesegmentsthatincludestheteams Every switch should...

Страница 11: ...ence team members will use to restore the line segment This is an optional step used to guide the restoration process Regardless of the alternate source sequence configu ration restoration progresses...

Страница 12: ...serial connection is RS232 with a DB9 pin connector If the computer only has USB ports use a serial to USB cable adapter NOTICE S C ships several types of software controlled products Make sure to use...

Страница 13: ...determine which jumper is correct for the distribution system Table 2 Distribution System Jumper Selection 3 Wires Grounding Type Use Uni grounded wye system Delta jumper s 4 Wires Grounding Type Use...

Страница 14: ...terior STEP 6 Check the battery using the following procedure The 5800 Series Switch Control is shipped with a Hawker Gates Monoblock 24 Vdc or 36 Vdc battery The battery is terminated with a connecto...

Страница 15: ...the IntelliLink Software section in Instruction Sheet 1042 530 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Setup STEP 2 If the switch control uses a modem fo...

Страница 16: ...d in pad mounted equip ment and the switch control is only powered from the sensors skip the remainder of this instruction sheet and go directly to Instruction Sheet 1042 530 S C 5800 Series Automatic...

Страница 17: ...ere elevated to primary high voltage Installers must follow the sequence of installation steps outlined in this chapter to ensure a safe and successful switch control installation STEP 3 Configure the...

Страница 18: ...the low voltage compartment as follows 1 Find the four studs on the wall of the low voltage compartment 2 Position the switch control so the four studs align with the four holes in the mounting flange...

Страница 19: ...nication and may optionally communicate with SCADA Installers must toggle the faceplate REMOTE LOCAL switch to the Local position to ensure the switch control does not perform remote switching command...

Страница 20: ...ew battery or the battery was shipped separately install it now WARNING If the enclosure heater was recently on the battery bracket may be hot Be careful not to touch a hot bracket The battery bracket...

Страница 21: ...With the ac line fuse still removed connect the red and black battery leads to the corresponding leads from the switch control This will supply dc voltage to the switch control For Scada Mate Switchin...

Страница 22: ...ts at J2 and J4 See Figure 14 For installations using three voltage sensors and nine current sensors the voltage input should be connected at J3 and the current inputs at J2 J4 and J6 See Figure 14 Ch...

Страница 23: ...ac line fuse is inserted the red AC ON and CHG ON LEDs should illuminate See Figure 13 on page 21 If the AC ON and CHG ON LEDs do not illuminate check the external ac voltage source if applicable The...

Страница 24: ...struction Sheet 1042 550 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Troubleshooting d Check that the LCD screen is backlit and that data are displayed Then...

Страница 25: ...rrecting the error condition continue with Step 6 STEP 5 For S C switches remove the yellow Sensor Calibration sheet that came with the switch There will be a sheet for each set of sensors Put a copy...

Страница 26: ...make sure the communications equipment has power For overhead switch controls the communication equipment is on the back of the faceplate For 5800 Series Switch Controls installed in pad mounted gear...

Страница 27: ...S C Instruction Sheet 1042 511 27 Installation Diagrams...

Страница 28: ...28 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 29: ...S C Instruction Sheet 1042 511 29 Installation Diagrams...

Страница 30: ...30 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 31: ...S C Instruction Sheet 1042 511 31 Installation Diagrams...

Страница 32: ...32 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 33: ...S C Instruction Sheet 1042 511 33 Installation Diagrams...

Страница 34: ...34 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 35: ...S C Instruction Sheet 1042 511 35 Installation Diagrams...

Страница 36: ...36 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 37: ...S C Instruction Sheet 1042 511 37 Installation Diagrams...

Страница 38: ...38 S C Instruction Sheet 1042 511 Installation Diagrams...

Отзывы: