TY-JS-220308-001
13
Order Code
Items
Value in Case 1 Value in Case 2
1
F0
Temperature setting
25
2
F1
Temperature Difference Values
-3
3
F2
Refrigeration return difference
0.5
2.0
4
F3
Way of control
1
0
5
F4
Alarm for over high water temperature
15
5
6
F5
Alarm for over low water temperature
15
10
7
F6
Alarm for over high room temperature
45
45
8
F7
Password
8
8
9
F8
The allowed highest water temperature
31
30
10
F9
The allowed lowest water temperature
25
5
11
F10
Flow 1 alarm value
0.5
0.5
12
F11
Flow 2 alarm value
0.5
0.5
Case 1: cooling water temperature is controlled by intelligent mode. Requiring water
temperature to be between 25
℃
to 31
℃
. Ambient temperature keeping constant, when
the set water temperature is 3
℃
lower than the ambient, the fluctuation will not exceed
±0.5
℃
. There will be an alert when water temperature is 10
℃
lower or higher than target
(e.g. when ambient temperature is 30.0
℃
, cooling water temperature is between 27.5
℃
to 26.5
℃
, if ambient temperature is up to 30.5
℃
, water temperature will be between
28.0
℃
to 27.0
℃
).
Case 2: cooling water temperature is controlled by constant mode. Requiring water
temperature is constant in 28
℃
, and the fluctuate does not exceed ±2
℃
. The alarm of
over high water temperature will be on when water temperature is 7
℃
(F4+F2) higher
than normal, and the alarm of over low water temperature will be on when water
temperature is 12
℃
(F5+F2) lower than normal.
VI. Alarm & Output Terminal
In order to guarantee the equipment will not be affected while abnormal situation
happens to the chillers, the chillers are designed with alarm protection function.
1.Alarm output terminals and wiring diagram
2.Alarm causes and working status table