(1) After turning on the power switch, the circulating pump of the chiller starts to work.

When the new machine is turned on for the first time, there will be more air bubbles in the

pipeline, which will cause the machine to alarm occasionally, and it will return to normal

after a few minutes of operation.

(2) After starting the machine for the first time, check if the water pipes leaks immediately.

(3) After turning on the power, if the water temperature is lower than the set temperature,

it is normal that the cooling fan and other devices of the machine do not work. The

temperature controller will automatically control the working status of compressors,

solenoid valves, cooling fans and other components according to the set parameters.

(4) As it takes a longer time to start over the compressor and other components,

according to different conditions, the time is range from seconds to minutes, so do not

turn off the power and again on frequently.

6.Electrical connection.

(1) Please select the cable based on the max. rated current indicated on the label of the
chiller.
(2) Recommended reference standard for power cord diameter selection.

Rated current/ A

≤5

≤10

≤15

≤25

≤35

≤50

Wire diameter (copper wire)/ mm²

1.0

1.5

2.5

4.0

6.0

10.0

Note: This data is provided according to IEC 60204-1 standard and only for
reference. Standard cables must be used in the power cord.

(3) The main circuit of the power supply must be equipped with appropriate electric
leakage and overload protection devices, and the chiller must be well grounded.
(4) Less than ±10% of power supply voltage fluctuation and less than ±1Hz of frequency
fluctuation are allowed, and keep away from electromagnetic interference sources.

7. Fill Water & Exhaust Air.

(1) Fill Water

After the new machine is turned on, the air in the water pipe is emptied, and the

water level of the water tank will drop slightly. In order to keep the water level in the

green area, you can add water again. Observe and write down the current water level.

After the chiller has been running for a period of time, observe the water level gauge

again. If the water level drops significantly, check again if there is leakage in the water

pipes.

Содержание CW-5000 Series

Страница 1: ...TY JS 220308 001 1 CW 5000 5200 Industrial Chiller User Manual...

Страница 2: ...rly so that you can refer to it whenever you need information This manual is not a quality guarantee Our company reserves the right to the interpretation of the correction of misprint and improperly d...

Страница 3: ...NTENTS Notice 4 I Overview 7 II Model Illustration 7 III Product Outlines Parts 8 IV Installation 9 V Operating States Parameters Adjustment 11 VI Alarm Output Terminal 13 VII Maintenance 14 VIII Simp...

Страница 4: ...on a The power supply must conform to the standard indicated in the nameplate or the manual b Use the standard cable and select the standard wire diameter c The grounding wire must be installed and th...

Страница 5: ...ailable Otherwise it may cause anesthesia and suffocation if a large amount of refrigerant fills the enclosed space b Avoid contacting with skin or it will cause frostbite DANGER Failure to take safet...

Страница 6: ...r filter at least once a week If it is blocked the cooling ability will decrease and the power consumption will increase and the alarm will not work properly Equipment surface cleaning a Please use cl...

Страница 7: ...chiller the refrigerant in the evaporator coil absorbs the heat of the return water and vaporizes into steam The compressor continuously extracts the generated steam from the evaporator and compresses...

Страница 8: ...rt names are only for one of the models and they will be slightly different in different models POWER SWITCH TEMPERATURE CONTROLLER AIR INLET FILTER GAUZE ALARM OUTPUT TERMINAL COOLING WATER OUTLET CO...

Страница 9: ...Requirements Cooling medium allowed by the chiller includes purified water distilled water high purity water and other softened water It is forbidden to use oily liquids liquids containing solid part...

Страница 10: ...on 1 Please select the cable based on the max rated current indicated on the label of the chiller 2 Recommended reference standard for power cord diameter selection Rated current A 5 10 15 25 35 50 Wi...

Страница 11: ...trolling parameters according to room temperature for meeting equipment cooling requirements The new T 504D intelligent temperature controller is selected constant temperature control mode as factory...

Страница 12: ...ey to change settings After modifying the value press the ENTER button RST to save and exit then new parameters take effect or press SET key SET to exit without saving parameters If there is no more a...

Страница 13: ...the ambient the fluctuation will not exceed 0 5 There will be an alert when water temperature is 10 lower or higher than target e g when ambient temperature is 30 0 cooling water temperature is betwe...

Страница 14: ...the air filter must not be missing for a long time VIII Simple Troubleshooting Failure Failure Cause Approach Machine turned on but unelectrified Power cord is not plugged in place Check and ensure th...

Страница 15: ...tlet and inlet To ensure a smooth ventilation for air outlet and inlet Voltage is extremely low or astable To improve the power supply circuit or use a voltage regulator Improper parameter settings on...

Отзывы: