TY-JS-220308-001
12
don’t release the buttons until the controller displays rE. The con troller works in normal
order in 6s and is restored to factory set tings.
3.Press
▼
key to show t1. Press
▼
key again to show room
temperature (Meanwhile D1 is flashing, displaying room temperature)
;
Continue to press
▼
key to show t2. Press
▼
key again to show flow rate 1.(Unit:
L/min)
;
Continue to press
▼
key to show t3. Press
▼
key again to show flow rate 2.(Unit:
L/min)
;
Continue to press
▼
key to exit display or restore to water temperature display in 6
seconds if no key is pressed.
4. Alarm function
(1) Alarm Display:
When alarm occurs, the error code and the temperature will be alternately displayed.
E1
E2
E3
E4
E5
E6
E7
Ultrahigh
room
temperature
Ultrahigh
water
temperature
Ultralow
water
temperature
Room
temperature
sensor
failure
Water
temperature
sensor
failure
Flow
rate
1
alarm
Flow
rate
2
alarm
(2) To suspend the alarm:
In alarming state, the alarm sound could be suspended by pressing any button, but
the alarm display remains until the alarm condition is eliminated.
5. General settings adjustment
Press SET button
(
SET
)
to enter into the user-defined state. Meanwhile, D1 flashes
to indicate that the controller is in parameters setup status.
(1)Under intelligent mode, the control panel displays the temperature difference value
between water and room (Factory setting is -2).
(2)At this moment, press ▲▼ key to change settings. After modifying the value, press the
ENTER button (RST) to save and exit, then new parameters take effect, or press SET
key (SET) to exit without saving parameters. If there is no more action within 20
seconds, it will automatically exit modifying status without saving parameters.
6. User parameter adjustment
Press and hold the ▲ key first, and then press "SET" key at the same time for 5 seconds
until 00 is displayed, at this time, press the ▲▼ key to select the set password (F7=8),
and then press "SET" key. If the password is correct, F0 is displayed, entering the setting
state. The panel indicator D1 flashes indicating the controller being in the parameter
setting state. If the password is wrong, it will return to temperature display. After entering
the setting state, Press the ▲ key to cycle into the selected items, and press ▼ key to
cycle in the opposite direction. (Only F0-F11 is displayed) Select the set item and then
press the "SET" key to enter the next parameter modification, and the original set value
is displayed. At this time, press ▲▼ key to modify the parameter value, and then press
"SET" key to return to the previous menu setting item. Press the "RST" key at any time to
save the modified parameters and exit, return to the temperature display, and run
according to the new parameters. If no key is pressed within 20 seconds, the controller
will automatically exit the parameter setting state without saving the modified
parameters. (In the parameter setting state, the system runs according to the parameters
adjusted immediately.)
7. Advanced parameters adjustment case