Performing leak test & insulation
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before recreating the vacuum and
recirculating the R410A, it’s responsible of installer to pressurize the whole
system with nitrogen (using a cylinder with pressure reducer) at a pressure above
30 bar (gauge).
LEAK TEST WITH R410A (after opening valves)
Before opening valves, discharge all the nitrogen into the system and
create vacuum. After opening valves check leaks using a leak detector for
refrigerant R410A.
Leak test
Insulation
Once you have checked that there are no leaks in the system,
you can insulate the piping and hose.
1
To avoid condensation problems, place
T13.0 or thicker Acrylonitrile
Butadien Rubber
separately around each refrigerant pipe.
Note
Always make the seam of pipes face upwards.
2
Wind insulating tape around the pipes and drain hose avoiding to compress
the insulation too much.
3
Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit.
4
The pipes and electrical cables connecting the indoor unit with the outdoor
unit must be fixed to the wall with suitable ducts.
No gap
NBR(T13.0 or thicker)
Insulation cover pipe
Indoor unit
Be sure to overlap
the insulation
CAUTION
Must fit tightly against body
without any gap.
Insulation pipe
All refrigerant connection must be accessible, in order to permit
either unit maintenance or removing it completely.
CAUTION
Discharge all the nitrogen to create a vacuum and charge
the system.
CAUTION