17
EN
G
LIS
H
Installation/Service mode
•
'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be
possible or it may not be applied though it is set on the unit.
•
If communication initialization is needed after saving the setting, the system will reset automatically and
communication will be initialized.
NOTE
Main
menu
Sub-
menu
Function
SEG
number
Default
Range
Unit
1
1
Wired remote
controller's option
function set /
Check 1
Cooling support Y / N
1
1
0-Both cooling & heating
1-Heating only
-
Selecting the standard
temperature of cooling
and heating
2
0
0-Water Outlet temperature
1-Indoor temperature
-
Selecting a standard
sensor of indoor
temperature
3
0
0-Temperature sensor of wired
remote controller 1-External
temperature sensor
-
Selecting Master/Slave
4
0
0-Master, 1-Slave
-
2
Wired remote
controller's option
function set /
Check 2
Allow self-test entering
Y / N
1
0
0-Entering is not allowable
1-Entering is allowable
-
3
Room temperature
compensation of
a wired remote
controller set /
check
Checking current sensor
temperature value
123
0
-9~40˚C(15.8~104˚F)
-
4
Setting compensation
temperature value
123
0
-9.9~9.9˚C(14.18~49.82˚F)
0.1˚C
(32.18˚F)
5
Checking the
number of
connected devices
The number of
connected devices
12
-
0~16
1
6
Setting desired temperature unit (Available
only when the temperature display is °C)
1
1
0-1˚C(33.8˚F), 1-0.5˚C(32.9˚F),
2-0.1˚C(32.18˚F)
-
0
Reset to option setting default value of wired
remote controller
1
0
0-Disuse, 1-Reset
-
2
1
Checking Micom code of wired remote
controller
1~6
-
Micom code
-
2
Checking version information of wired remote
controller
1~6
-
Revision date
-
3
1
Checking Hydro Unit main address
12
-
Main address(0~63)
Display the main address
currently applied
Setting Hydro Unit main address
34
-
Main address(0~63)
(When the address setting
is set as manual address, the
corresponding address will be
set after the outdoor unit is reset
and tracking is completed.)
2
Hydro Unit group(RMC) address set/check
12
-
Group address (00H~2FH)
3
Wireless remote controller option set/check
-
-
Option code
4
Hydro Unit option(K1~K24) set / check
-
-
Option code
0
Process initialization
1
0
0-Disuse, 1-Reset
-
DVM Hydro Unit_MWR-WW00_IM_EN_03647A(1).indd 17
2013-01-09 오후 2:48:43