Wiring works
Selection for the power and booster heater wire terminal
f
f
Connect the cables to the terminal board using the solderless ring terminal .
f
f
Use certified and verified cables .
f
f
Connect using a driver which is able to apply the rated torque to the screws .
f
f
If the terminal is loose, fire may occur caused by arc .
If the terminal is connected too firmly, the terminal may be damaged .
f
f
External force should not be applied to the terminal block and wires .
f
f
The cable ties to fasten the wire should be an incombustible material, V0 or above .
(The cable ties should be used to fasten the power wire and they are supplied with the unit .)
Tightening Torque (kgf • cm)
M3
0 .5 ~ 0 .75
M3 .5
8 ~ 12
M4
12 ~ 18
M5
20 ~ 30
f
f
Main PCB
M4 Screw
M3 .5 Screw
M3 .5 Screw
M3 Screw
f
f
ELCB
M5 Screw
12
EHS MONO Kit-EU_IM_05388A-00_EN.indd 12
2015-03-18 오전 11:53:35