Refrigerating Cycle Diagram
6
6-1-3. Main parts status
1. Digital scroll compressor
The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps.
2. Accumulator
To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back).
3. Receiver
To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control the amount of
refrigerant during the individual operation of indoor unit.
4. Solenoid valve (PWM)
It is installed at the top of digital scroll compressor and at the low pressure pipe, which is used for operating the digital scroll
compressor. When the valve is open, the digital scroll compressor keeps the state of unloading.
5. Solenoid valve (HGBV)
When the low pressure gets lower, the valve is open by the low pressure safety device. The valve is open in order to reduce
the load at the start of compressor and when the system stops and then keep the balance of low pressure.
6. Solenoid valve (LBV)
When the compressor is overheated, it actuates to lower the temperature of compressor for stable operation.
7. Solenoid valve (VBV)
The valve is open in order to reduce the load at the start of compressor and when the system stops and then keeps the
balance of low pressure.
8. High pressure switch
To stop the system for the system protection when the high pressure exceeds the set value.
9. Low pressure switch
To stop the system for the system protection when the low pressure falls below the set value.
10. Temperature sensor (DTS, Discharge Temperature Sensor)
10.
It is the means to measure the refrigerant temperature of compressor outlet which is used as the data for control of
compressor.
11. Temperature sensor (CMS, Condenser Mid Sensor)
10.
It is the detection means to do the optimum control of outdoor fan, which is used as the data for each
protection or initial startup.
12. Temperature sensor (COS, Condenser Out Sensor)
10.
It is used as the detection for calculation of over-cooling at the condenser outlet which is referred for the
adjustment of refrigerant during refrigerant charging.
13. Temperature sensor (OATS, Outdoor Air Temperature Sensor)
10.
To measure the outdoor temperature which is used for the determination of start method.
14. Fixed scroll compressor
10.
The fixed capacity type compressor.
15. Temperature sensor (FDTS, Fixed Discharge Temperature Sensor)
10.
It is the means to measure the refrigerant temperature of compressor outlet which is used as the data for control of fixed
compressor.
16. Low pressure sensor (LPSO)
10.
By measuring the low pressure, any abnormal system status is determined and the low-pressure
protection control is performed.
17. High pressure sensor (HPSO)
10.
By measuring the high pressure, any abnormal system status is determined and the high-pressure
protection control is performed.
18. Oil separator
10.
This device recovers oils emitted from the compressor and returns it to the compressor again.
19. Oil sensor (OIL.S)
10.
To control EEV against liquid back and low dilution of oil to protect the compressor by measuring
the temperature of oil used for controlling SUMP at low temperature in cooling / heating mode.
DB98-17816A(1)_6~7 3/2/04 9:33 AM Page 146
Содержание DVM Series
Страница 76: ... 75 Memo ...
Страница 112: ......
Страница 113: ......
Страница 156: ... 155 Memo ...
Страница 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Страница 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Страница 285: ... 284 Exploded Views and Parts List 9 ...
Страница 286: ... 285 Exploded Views and Parts List 30 3 30 5 30 10 30 2 30 4 30 1 30 8 30 7 30 6 30 9 56 1 56 2 56 3 56 4 ...
Страница 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Страница 291: ... 290 Exploded Views and Parts List 9 ...
Страница 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Страница 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Страница 309: ... 308 Exploded Views and Parts List 9 4 6 3 1 5 7 8 10 9 11 2 9 2 2 1 Way cassette type panel cont ...
Страница 349: ... 348 Exploded Views and Parts List 9 6 9 8 7 5 2 3 2 1 5 1 4 5 3 5 4 5 9 2 16 Floor Standing type Ass y Panel Outlet ...
Страница 353: ... 352 Exploded Views and Parts List 9 4 2 3 6 11 10 9 5 1 7 7 1 7 2 7 3 8 9 2 18 Floor Standing type Ass y Inlet ...
Страница 358: ... 357 Memo ...
Страница 360: ... 359 359 Heat pump AVMKH Wiring Diagram This Document can not be used without Samsung s authorization ...
Страница 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Страница 362: ... 361 Heat pump AVMCH ...
Страница 366: ... 365 Wiring Diagram 10 1 4 Wall mounted type AVMWC AVMWH This Document can not be used without Samsung s authorization ...
Страница 367: ... 366 Wiring Diagram 10 10 1 5 Ceiling type AVF This Document can not be used without Samsung s authorization ...
Страница 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Страница 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Страница 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Страница 372: ... 371 Wiring Diagram 10 2 2 Heat pump 050 060 This Document can not be used without Samsung s authorization ...
Страница 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Страница 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Страница 375: ... 374 Wiring Diagram 10 RMAH140 160 180 200 This Document can not be used without Samsung s authorization ...
Страница 376: ... 375 Wiring Diagram RMAH200 240 260 280 300 This Document can not be used without Samsung s authorization ...
Страница 378: ... 377 Schematic Diagram 11 1 2 4 Way cassette type AVMCC H This Document can not be used without Samsung s authorization ...
Страница 380: ... 379 Schematic Diagram AVMWC H 052 072 This Document can not be used without Samsung s authorization ...
Страница 382: ... 381 Schematic Diagram 11 1 5 Floor Standing type AVMPC H This Document can not be used without Samsung s authorization ...
Страница 383: ... 382 Schematic Diagram 11 11 1 6 Ceiling type This Document can not be used without Samsung s authorization ...
Страница 384: ... 383 Schematic Diagram 11 1 7 Cooling only 060 070 This Document can not be used without Samsung s authorization ...
Страница 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Страница 389: ... 388 Memo ...