4. The outdoor unit starts a tracking to check the connected indoor unit and option at power ON.
●
The left of outdoor unit PCB check display part checks the
responded indoor unit by communication to 0~F address,
and displays the responded address to the right of PCB
check display part.
●
Check if the indoor unit address at installation and the indoor
unit address responded is same.
●
Check if the number of indoor unit installed and the number
of outdoor unit PCB setup is same.
●
If the number of indoor unit set on outdoor unit PCB and
responded by communication is same after tracking, go
ahead the next step.
●
If CH is displayed on the part of outdoor unit PCB check
display after completion of tracking, the compressor is not
preheated. Turn the power On to heat the compressor, and
wait until the CH is disappeared.
●
The communication between the indoor unit and the outdoor unit is performed if the compressor is preheated. And the
connected indoor unit address is displayed at the right of the outdoor unit PCB check display part.
5. Check the system pressure by use of manifold gauge.
●
Connect the manifold gauge with the high/low pressure
service valve of outdoor unit.
●
Check if the high/low pressure service valves are all opened.
●
Operate the system by pressing the refrigerant charge key.
●
Check the high/low pressure through the manifold gauge.
●
Refer to the pressure table classified by the outdoor
temperature and the length of drain pipe provided separately
for a proper pressure.
●
Stop the system by pressing the refrigerant charge key.
Check if the indoor unit address is responded as a same.
- 66 -
Installation
4
Left Right
PCB display part
High pressure side
Mani hold gauge
Low pressure
side
• E2 is displayed on the part of outdoor unit PCB check display if the tracking is failed.
• Perform the re-tracking by pressing KEY 3 after checking address of indoor and outdoor unit.
• Check the input value after 30 minutes after running the compressor because the high/low is changed
continually at the initial operation.
• Don't perform the system operation more than 1 hour to check system pressure.
DB98-17816A(1)_1~4 3/2/04 9:31 AM Page 66
Содержание DVM Series
Страница 76: ... 75 Memo ...
Страница 112: ......
Страница 113: ......
Страница 156: ... 155 Memo ...
Страница 280: ... 279 Exploded Views and Parts List 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Страница 281: ... 280 Exploded Views and Parts List 9 F Type cont 31 1 56 1 31 5 31 4 31 3 31 2 56 2 57 ...
Страница 285: ... 284 Exploded Views and Parts List 9 ...
Страница 286: ... 285 Exploded Views and Parts List 30 3 30 5 30 10 30 2 30 4 30 1 30 8 30 7 30 6 30 9 56 1 56 2 56 3 56 4 ...
Страница 287: ... 286 Exploded Views and Parts List 9 31 1 31 4 31 2 31 5 31 6 31 3 57 1 57 2 58 G Type cont ...
Страница 291: ... 290 Exploded Views and Parts List 9 ...
Страница 292: ... 291 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 31 3 62 1 62 2 63 1 63 2 ...
Страница 298: ... 297 Exploded Views and Parts List 31 1 31 6 31 5 31 4 31 2 61 1 61 2 62 1 65 2 31 3 ...
Страница 309: ... 308 Exploded Views and Parts List 9 4 6 3 1 5 7 8 10 9 11 2 9 2 2 1 Way cassette type panel cont ...
Страница 349: ... 348 Exploded Views and Parts List 9 6 9 8 7 5 2 3 2 1 5 1 4 5 3 5 4 5 9 2 16 Floor Standing type Ass y Panel Outlet ...
Страница 353: ... 352 Exploded Views and Parts List 9 4 2 3 6 11 10 9 5 1 7 7 1 7 2 7 3 8 9 2 18 Floor Standing type Ass y Inlet ...
Страница 358: ... 357 Memo ...
Страница 360: ... 359 359 Heat pump AVMKH Wiring Diagram This Document can not be used without Samsung s authorization ...
Страница 361: ... 360 Wiring Diagram 10 10 1 2 4 way cassette type Cooling only AVMCC ...
Страница 362: ... 361 Heat pump AVMCH ...
Страница 366: ... 365 Wiring Diagram 10 1 4 Wall mounted type AVMWC AVMWH This Document can not be used without Samsung s authorization ...
Страница 367: ... 366 Wiring Diagram 10 10 1 5 Ceiling type AVF This Document can not be used without Samsung s authorization ...
Страница 369: ... 368 Wiring Diagram 10 070F This Document can not be used without Samsung s authorization ...
Страница 370: ... 369 Wiring Diagram 080 100 This Document can not be used without Samsung s authorization ...
Страница 371: ... 370 Wiring Diagram 10 100F This Document can not be used without Samsung s authorization ...
Страница 372: ... 371 Wiring Diagram 10 2 2 Heat pump 050 060 This Document can not be used without Samsung s authorization ...
Страница 373: ... 372 Wiring Diagram 10 080 100 This Document can not be used without Samsung s authorization ...
Страница 374: ... 373 Wiring Diagram 100F This Document can not be used without Samsung s authorization ...
Страница 375: ... 374 Wiring Diagram 10 RMAH140 160 180 200 This Document can not be used without Samsung s authorization ...
Страница 376: ... 375 Wiring Diagram RMAH200 240 260 280 300 This Document can not be used without Samsung s authorization ...
Страница 378: ... 377 Schematic Diagram 11 1 2 4 Way cassette type AVMCC H This Document can not be used without Samsung s authorization ...
Страница 380: ... 379 Schematic Diagram AVMWC H 052 072 This Document can not be used without Samsung s authorization ...
Страница 382: ... 381 Schematic Diagram 11 1 5 Floor Standing type AVMPC H This Document can not be used without Samsung s authorization ...
Страница 383: ... 382 Schematic Diagram 11 11 1 6 Ceiling type This Document can not be used without Samsung s authorization ...
Страница 384: ... 383 Schematic Diagram 11 1 7 Cooling only 060 070 This Document can not be used without Samsung s authorization ...
Страница 385: ... 384 Schematic Diagram 11 050 This Document can not be used without Samsung s authorization ...
Страница 389: ... 388 Memo ...