44
3
Placing the outdoor units
3-1. Anchor bolts position
3-2. Removing fasteners of compressor’s leg
(Only applied to RVXVHT125F
)
(1) Open the bottom cabinet with screw driver.
The compressors are fastened with nuts in 4 places of only
following models.
RVXVHT125F
(2) Detach nut washer, washer and stopper nut from
compressors with a tool.
(3) Refasten the nut washer only.
Nut washer
Washer Stopper nut
Remove
Model
RVXVHT075/100
RVXVHT125
A
880(34-5/8)
1200(47-1/4)
B
738(29)
1058(41-5/8)
A
Anchor bolt
745(29-5/16)
765(30-1/8)
B
Unit : mm(inch)
Pay your attention not to touch the copper pipes as detaching the fasteners.
The stopper nut and washer should be removed.
If this work is not conducted correctly, it can cause outdoor unit to vibrate and make much noise.
CAUTION
Содержание DVM PLUS III
Страница 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Страница 2: ......
Страница 3: ...Outdoor Units...
Страница 6: ...4 DVM PLUS III...
Страница 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Страница 62: ...DVM DVM Technical Data Book...
Страница 63: ......