• Additional refrigerant has to be charged according to the length and size of
liquid pipe.
• Example of additional refrigerant charging.
Pipe length is as below without distribution kit.
Ø12.70(1m/3.3ft)
Ø12.70(5m/16.4ft) Ø19.05(5m/16.4ft)
Ø15.88(10m/32.8ft)
Ø15.88(15m/49.2ft)
Ø12.70(15m/49.2ft)
Ø9.52(5m/16.4ft)
Ø9.52(5m/16.4ft)
Ø6.35(5m/16.4ft)
Ø6.35(5m/16.4ft)
Ø6.35(5m/16.4ft)
Ø9.52(7m/22.9ft)
Ø9.52(8m/26.2ft)
Liquid pipe size
(O.D.)
Additional
refrigerant charging
mm
inches
kg/m
lbs/ft
Ø6.35
Ø1/4
0.020
0.0134
Ø9.52
Ø3/8
0.060
0.0403
Ø12.70
Ø1/2
0.125
0.0840
Ø15.88
Ø5/8
0.180
0.1210
Ø19.05
Ø3/4
0.270
0.1814
Ø22.23
Ø7/8
0.350
0.2352
Outdoor unit
Factory charging
kg
lbs
RVXVHT075FE
6.5
14.330
RVXVHT100FE
7.5
16.535
RVXVHT125FE
9.0
19.824
Additional refrigerant charging of
distribution kit (kg/m)
kg/m lbs/ft
Remarks
Regardless of the liquid pipe size,
additional refrigerant charging is
0.01kg(0.0067lbs) per meter(ft) after
distribution kit.
0.01 0.0067
For wall-mounted &
ceiling Indoor unit
Liquid pipe size (O.D.)
Total piping
lengths
Additional
refrigerant charging
mm
inches
m
ft
kg
lbs
Ø6.35
Ø1/4
15
49.21
0.300
0.6614
Ø9.52
Ø3/8
25
82.02
1.500
3.3069
Ø12.70
Ø1/2
21
68.90
2.625
5.7871
Ø15.88
Ø5/8
25
82.02
4.500
9.9208
Ø19.05
Ø3/4
5
16.40
1.350
2.9762
Total
10.275
22.652
6-5. Additional refrigerant charging
Total refrigerant amount of the system must be less then 100kg(220lbs). If total refrigerant amount of system is over
100kg(220lbs) more, the system has to be divided into smaller system, each containing less than 100kg(220lbs).
CAUTION
Содержание DVM PLUS III
Страница 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Страница 2: ......
Страница 3: ...Outdoor Units...
Страница 6: ...4 DVM PLUS III...
Страница 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Страница 62: ...DVM DVM Technical Data Book...
Страница 63: ......