4
Electric specifications
4-1. Basic models
4-2. Combinations
Classification
Capacity (Ton)
Capacity (HP)
Model
MCCB(A)
ELB
Single unit
6
7.5
RVXVHT075FE
50
50A, 30mA 0.1 Second or less
8
10.0
RVXVHT100FE
50
50A, 30mA 0.1 Second or less
10
12.5
RVXVHT125FE
60
60A, 30mA 0.1 Second or less
Model
Units
Power supply
Comp.
OFM
Hz
Volts
Min.
Max.
MCA
MFA
RLA
kW
FLA
RVXVHT075FE
60
208~230
187
253
48.1
50
13.8 + 21.8
0.63
7
RVXVHT100FE
60
208~230
187
253
53.8
50
19.6 + 21.8
0.63
7
RVXVHT125FE
60
208~230
187
253
61.1
60
23.4 + 24.6
0.63
7
Classification Capacity
(Ton)
Capacity
(HP)
Basic model
MCCB(A)
ELB
RVXVHT075FE
RVXVHT100FE
RVXVHT125FE
Module unit
12
15.0
2
50 + 50
14
17.5
1
1
50 + 50
16
20.0
2
50 + 50
18
22.5
1
1
50 + 60
20
25.0
2
60 + 60
22
27.5
1
2
50 + 50 + 50
24
30.0
3
50 + 50 + 50
26
32.5
2
1
50 + 50 + 60
28
35.0
1
2
50 + 60 + 60
30
37.5
3
60 + 60 + 60
Model
Units
Power supply
Comp.
OFM
Hz
Volts
Min. Max.
MCA
MFA
RLA
kW
FLA
RVXVHT150FE 60 208~230 187
253
96.2
50+50
(13.8+21.8)×2
0.63+0.63
7+7
RVXVHT175FE 60 208~230 187
253
101.9
50+50
(13.8+21.8)+(19.6+21.8)
0.63+0.63
7+7
RVXVHT200FE 60 208~230 187
253
107.6
50+50
(19.6+21.8)×2
0.63+0.63
7+7
RVXVHT225FE 60 208~230 187
253
114.9
50+60
(19.6+21.8)+(23.4+24.6)
0.63+0.63
7+7
RVXVHT250FE 60 208~230 187
253
122.2
60+60
(23.4+24.6)×2
0.63+0.63
7+7
RVXVHT275FE 60 208~230 187
253
155.7 50+50+50 (13.8+21.8)+(19.6+21.8)×2 0.63+0.63+0.63 7+7+7
RVXVHT300FE 60 208~230 187
253
161.4 50+50+50
(19.6+21.8)×3
0.63+0.63+0.63 7+7+7
RVXVHT325FE 60 208~230 187
253
168.7 50+50+60 (19.6+21.8)×2+(23.4+24.6) 0.63+0.63+0.63 7+7+7
RVXVHT350FE 60 208~230 187
253
176.0 50+60+60 (19.6+21.8)+(23.4+24.6)×2 0.63+0.63+0.63 7+7+7
RVXVHT375FE 60 208~230 187
253
183.3 60+60+60
(23.4+24.6)×3
0.63+0.63+0.63 7+7+7
All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.
The relationship between the starting time and the starting current (Digital Scroll Comp. + Fixed Scroll Comp)
RLA is based on the following conditions.
- Indoor temp. : 80˚F DB/ 67˚F WB
- Outdoor temp. : 95˚F DB
Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage variation between phases is 2%.
Select wire size based on the value of MCA.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
Abbreviations
- MCA: Min. Circuit Amps. (A)
MCA = 1.25 X LOAD1 + LOAD2
(LOAD1: RLA of Digital Comp. / LOAD2: RLA of Fixed Comp. + FLA of Fan Motor)
- MFA: Max. Fuse Amps. (A)
- RLA: Rated Load Amps. (A)
- OFM: Outdoor Fan Motor
- FLA: Full Load Amps. (A)
- kW : Rated Motor Output (kW)
St
ar
tin
g
cu
rre
nt
Starting time
RLA
Содержание DVM PLUS III
Страница 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Страница 2: ......
Страница 3: ...Outdoor Units...
Страница 6: ...4 DVM PLUS III...
Страница 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Страница 62: ...DVM DVM Technical Data Book...
Страница 63: ......