Option switches & function keys
7-1. Option switches
0123
45
6789
A BC
D
EF
Switch
Setting
Function
Remarks
SW01/SW02
Setting total quantity of Installed indoor units
Main unit required only
SW01 : The tens digit, SW02 : The units digit
Main unit required only
Ex) As 12 indoor units were installed,
SW01:1, SW02: 2
SW03
K5
On
Manual address setting
Off
Auto address setting
SW04
K9
K10
Target evaporating temperature (°C/°F)
Cooling capacity compensation
On
On
7~9(44.6 ~ 48.2)
On
Off
5~7(41.0~44.6)
Off
On
9~11(48.2~51.8)
Off
Off
10~12(50.0~53.6)
SW04
K11
K12
Target high pressure (kg
f
/cm
2
, psig, kPa)
On
On
30.0, 426, 2941
Heating capacity compensation
On
Off
31.5, 448, 3089
Off
On
33.0, 469, 3236
Off
Off
27.0, 384, 2647
SW05
K13
K14
Outdoor unit’s address
On
On
Outdoor unit’s address : No 1
Main unit
On
Off
Outdoor unit’s address : No 2
Sub I unit
Off
On
Outdoor unit’s address : No 3
Sub 2 unit
Off
Off
Outdoor unit’s address : No 4
Sub 3 unit
K15
K16
Maximum current control
On
On
Standard
Factory default
On
Off
90% of standard peak current value
Off
On
80% of standard peak current value
Off
Off
Not use
SW06
K17
On
Since supplying power, first oil return operation happens after 5hrs and then 7 hrs.
Off
Since supplying power, first oil return operation happens after 2hrs and then 2 hrs.
K18
On
Standard
Defrost period setting
Off
Shorten defrost period by 20% approximately
K19
On
Standard fan step
Off
Fan step compensation (Maximum step)
7.5/10 HP : 19 Steps, 12.5 HP : 23 Steps
K20
On
Normal
Off
Night’s quiet mode
Factory default
SW01, SW02, SW09 : ‘0’
SW03 ~ SW06 : ON
Содержание DVM PLUS III
Страница 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Страница 2: ......
Страница 3: ...Outdoor Units...
Страница 6: ...4 DVM PLUS III...
Страница 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Страница 62: ...DVM DVM Technical Data Book...
Страница 63: ......