Error codes
No. Error code
Description
34
E-210
Communication error between MCU and outdoor unit.
35
E-211
Indoor unit’s address overlapped on the MCU.
35
E-213
No matching between installed indoor unit’s address and indoor unit’s address on the MCU.
35
E-214
Setting error of MCU’s quantity in outdoor unit’s PCB
36
E-215
Indoor unit’s address setting error on the MCU. (There is same address among the MCUs)
37
E-216
Setting error of indoor unit activating dip switch on MCU’s PCB. (The indoor unit is not connected with the
MCU’s port but indoor unit activating dip switch on MCU’s PCB turns on.)
38
E-217
Setting error of indoor unit activating dip switch on MCU’s PCB. (The indoor unit is connected with the
MCU’s port but indoor unit activating dip switch on MCU’s PCB turns off.)
39
E-218
Setting error of indoor unit’s quantity on MCU’s PCB.
(The quantity of installed indoor units exceeds the setting number of the MCU’s PCB.)
40
E-221
Ambient air temperature sensor of outdoor unit. (Open or Short)
41
E-226
Ambient air temperature sensor is detached from outdoor unit.
42
E-231
Cond_out temperature sensor of main outdoor unit. (Open or Short)
43
E-236
Cond_out temperature sensor of the outdoor unit. (Open or Short)
44
E-237
Cond temperature sensor of outdoor unit. (Open or Short)
45
E-241
Cond_mid temperature sensor is detached from sensor hold of the pipe.
46
E-246
Cond_out 1 temperature sensor is detached from sensor hold of the pipe.
47
E-251
Discharge temperature sensor of compressor 1. (Open or Short)
48
E-256
Discharge temperature sensor of compressor 1. (Open or Short)
49
E-257
Discharge temperature sensor of compressor 2. (Open or Short)
50
E-258
Discharge temperature sensor of compressor 3. (Open or Short)
51
E-261
Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
52
E-262
Discharge temperature sensor of compressor 1 is detached from the sensor hold of the pipe.
53
E-263
Discharge temperature sensor of compressor 2 is detached from the sensor hold of the pipe.
54
E-264
Discharge temperature sensor of compressor 3 compressor is detached from the sensor hold of the pipe.
55
E-265
Sump(Base) temperature sensor of main unit’s compressor is detached from the base of the compressor.
56
E-266
Sump(Base) temperature sensor of sub1 unit’s compressor is detached from the base of the compressor.
57
E-267
Sump(Base) temperature sensor of sub2 unit’s compressor is detached from the base of the compressor.
58
E-268
Sump(Base) temperature sensor of sub3 unit’s compressor is detached from the base of the compressor.
58
E-269
Suction temperature sensor is detached from the sensor hold of the pipe.
59
E-271
Sump(Base) temperature sensor of compressor 1. (Open or Short)
60
E-276
Sump(Base) temperature sensor of compressor 1. (Open or Short)
61
E-277
Sump(Base) temperature sensor of compressor 2. (Open or Short)
62
E-278
Sump(Base) temperature sensor of compressor 3. (Open or Short)
63
E-291
High pressure sensor. (Open or Short)
64
E-296
Low pressure sensor. (Open or Short)
65
E-307
Oil balance temperature sensor. (Open or Short)
66
E-308
Suction temperature sensor. (Open or Short)
67
E-311
Double tube / Liquid temperature sensor. (Open or Short)
68
E-312
Main cooling solenoid valve opening error.
69
E-321
EVI_in temperature sensor. (Open or Short)
70
E-322
EVI_out temperature sensor. (Open or Short)
71
E-407
Compressor stop by high pressure’s protection control.
72
E-410
Compressor stop by low pressure’s protection control.
73
E-413
Protection control by sump sensor.
74
E-416
Compressor stop by discharge temperature’s protection control.
75
E-425
Reverse phase or phase open. (3ø Wiring of outdoor unit, R-S-T-N)
76
E-428
Compressor stop by abnormal compression ratio.
77
E-431
Self-diagnosis of oil solenoid valve. (Open and Close error)
78
E-438
EVI EEV opening error.
79
E-440
Prohibition of heating operation when the ambient air temperature is over 30°C
80
E-442
Prohibition of refrigerant charging with heating operation when outdoor ambient air temperature is over 15°C.
81
E-443
Prohibition of operating when the high pressure of system is too low.
82
E-452
Power failure temporarily or zero crossing error.
Содержание DVM PLUS III
Страница 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Страница 2: ......
Страница 3: ...Outdoor Units...
Страница 6: ...4 DVM PLUS III...
Страница 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Страница 62: ...DVM DVM Technical Data Book...
Страница 63: ......