Test run and final check
Test Run
Final Check and Explaining operation to the owner
1. Please do cool mode try-run or heat mode try-run.
◆
Cool mode try-run : Push the [K2] button three times.
◆
Heat mode try-run : Push the [K2] button once.
2. After 12 minutes of stationary condition check each indoor unit air treatment.
◆
Cooling mode (indoor unit check)
Inlet air temp. - Outlet air temp : From 10°K to 12°K (indicative delta T)
◆
Heating mode (indoor unit check)
Outlet air temp. - Inlet air temp : From 11°K to 14°K (indicative delta T)
≫
In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space.
Before leaving the premises on which you have installed the air conditioner, you should explain the following operations
to the owner, making reference to appropriate pages in the owner's instruction booklet.
1. How to start and stop the air conditioner.
2. How to select the operating mode and adjust the temperature and fan settings.
3. How to adjust the air flow direction.
4. How to set the timers.
5. How to remove and clean the filters.
≫
Once the owner is happy with the basic operations, hand over the owner's instruction booklet and this installation
manual for storage in a handy and safe place.