A
Ampere Limit Setting & Changing Procedure
Ampere
Switch Selection
RJ100F5HX
**
AJ100FCJ5
**
Switch
3
4
23A
(OFF)
On
On
20A
(OFF)
On
Off
18A
(OFF)
Off
On
16A
(OFF)
Off
Off
It could take maximum 60 minutes to operate for the protection of the compressor if the outdoor
temperature is below -5°C.
<Outdoor PCB Display>
Setting installation option
◆
Do not adjust the “Ampere Limit Switch(DIP Switch)”, if it’s not
necessary : before modifying it, evaluate the total number of electric
and electronics loads consumption and use “Ampere limits switch(DIP
Switch)” just as emergency solution or in case the system is anyway
oversized compared to real thermal load needed.
◆
“Ampere Limit Switch(DIP Switch)” is initially set to the default value
(table below).
◆
“Ampere Limit Switch(DIP Switch)” is on the PCB of outdoor unit.
◆
Contact the authorized service technician or dealer for setting and
changing the “Ampere Limit Switch(DIP Switch)”.
◆
Before changing the “Ampere Limit Switch(DIP Switch)”, turn off the
main power of the system.