26
A
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power
supply in the indoor unit.
2. The panel (display) should be connected to an indoor unit to receive option.
3. Befofe installing the indoor unit, assign an option to the indoor unit according
to the airconditioning system plan.
- The default setting of an indoor unit installation option is “02000-100000-
200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an
indoor unit individually when there is more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
- When entering address option, connect remote controller receiver.
▶
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
1)
The window on/off function applies to the following unit
- AJN**/AR**
Indoor Unit
1(L)
F2
2(N)
F1
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Central control
Indication
and Details
Indication Details Indication
Details
Indication Details Indication Details Indication Details Indication Details
0
2
0
0
0
Disuse
0
1
Use
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Master/Slave
Indication
and Details
Indication Details Indication
Details
Indication Details Indication Details Indication Details Indication Details
1
0
0
0
0
0
Slave
1
Master
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
External control
External control output
Buzzer
Indication
and Details
Indication Details Indication
Details
Indication Details Indication Details Indication Details Indication Details
2
0
Disuse
0
Thermo
ON
0
0
Use
0
1
On/Off control
2
Off control
1
Operation
ON
1
Disuse
3
Window On/
Off control
1)
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Indication
and Details
Indication Details Indication
Details
Indication Details Indication Details Indication Details Indication Details
3
0
0
0
0
0
◆
AQV**/AJN**/AR**
No.
Function
On
Off
Remark
SW05
K1
External room sesor
Disuse
Use
K2
Centralized controller
Disuse
Use
K3
Compensate RPM
Standard
Up
Only MH**FS/FU**, NJ***LHX**
K4
Drain Pump
Disuse
Use
Only MH**FS/FU**, NJ***LHX**
SW06
K5
Indoor Temperature
Compensation for Heating Mode
+2°C
+5°C
+5°C
+2°C
Only MH***FM**
K6
Filter Time
1,000h
2,000h
Except MH***FV/FN/FB/FA/FJ**
K7
Hot Water Coil
Disuse
Use
Only MH**FS/FU**, NJ***LHX**
K8
-
-
-
SW07
K9
-
-
-
K10
-
-
-
K11
External Control
Disuse
Use
K12
External Control Output
Thermal ON Operation ON
How to use additional function
K1 K2 K3 K4
SW05
K5 K6 K7 K8
SW06
K9 K10 K11 K12
SW07
RJ100F5HXEA_IM_E_32978A(4).indd 26