Method for connecting wires
Specification for circuit breaker and power supply cord
≫
Power supply cord is not supplied with air conditioner.
≫
Select the power supply cord in accordance with relevant local and national regulations.
≫
Wire size must comply with the applicable local and national code.
≫
Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
Notes
1. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
2. Select power supply cord based on MCA.
3. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
4. MCA represents maximum input current.
5. MFA represents capacity which may accept MCA.
6. Communication Cable Specification: 2G. 0.75mm
2
or more.
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
1(L) 2(N)1(L) 2(N)
A
B
1(L) 2(N) F1 F2
1(L) 2(N) F1
1(L) 2(N) F1
1(L) 2(N) F1
F2
1 2
F1 F2
F1 F2
1 2
2
1
F2
1 2
F1 F2
F1 F2
F2
F1 F2
F1 F2
1 2
1 2
1
2
B
C
B
C
B
C
B
C
A
1(L) 2(N) F1 F2
F1 F2
F1 F2
1 2
B
C
1(L) 2(N)1(L) 2(N)1(L) 2(N)
F1 F2
F1 F2
F1 F2 F1 F2
L
N
1 2
2
1
2
1
C
B
D
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
Earth
terminal
A-unit
B-unit
C-unit
D-unit
E-unit
Indoor unit
Assembly cable
Outdoor unit
Main Power
Supply cable
Power cable to indoor units
Communication cable
to indoor units
A
Cable Type : A
B
Cable Type : B
C
Cable Type : C
Earth
terminal
Connecting wires
Model
Outdoor Units
Maximun Input Current [A]
Power Supply
Rated
Outdoor Unit
Indoor Unit
Hz
Volts
Outdoor
Indoor(Max.)
Total
MCA
MFA
RJ100F5HX**
AJ100FCJ5**
5 ROOM
50
1phase, 220-240
23.0
3.2
26.2
26.2
28.8
RJ100F5HXEA_IM_E_32978A(4).indd 13
2012-10-25 오후 5:22:45