98
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Emergency
operation for
compressor
malfunction
Individual
0
0
0
0
Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
0
1
Set compressor 1 as
malfunction state
0
2
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main
0
1
0
0
7-9 (Factory default in case
of A type PBA)
Targeted evaporation
ϩʪ͔ΧʪθɇϩЇθʪࣈঌAࣉ
(When low temperature
value is set, discharged air
temperature of the indoor
unit will decrease)
0
1
5-7 (Factory default in case
of B type PBA)
0
2
9-11
0
3
10-12
0
4
11-13
0
5
12-14
0
6
13-15
Capacity
correction for
heating
Main
0
2
0
0
3.0 (Factory default)
Targeted high pressure
[MPa].
(When low pressure value
is set, discharged air
temperature of the indoor
unit will decrease)
0
1
2.5
0
2
2.6
0
3
2.7
0
4
2.8
0
5
2.9
0
6
3.1
0
7
3.2
0
8
3.3
Current
restriction rate
Individual
0
3
0
0
100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection
interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the
product is being installed
in humid area such as near
river or lake
Fan speed
correction for
outdoor unit
Individual
0
6
0
0
Factory default
0
1
Increase fan speed
Increase the outdoor unit's
fan speed to maximum
value
Setting outdoor unit option switch and key function