42
Refrigerant pipe installation
H/R
(A)
(B)
ߥߥߨऌ̧Ǯ ߦߢߢऌ̧Ǯ
(D)
(E)
(F)
(C)
(3)
(2)
(1)
ߨߣߨऌ̧Ǯ
kу࣒ߣߥߧߤ̧Ǯ
Capacity (kW)
Ęͱ
Pipe size (mm)
Liquid pipe
Low pressure
gas pipe
High pressure
gas pipe
ߥߥߨऌ̧Ǯ
(1)
Ø 12.70
Ø 28.58
Ø 19.05
ߩߥߨऌ̧Ǯ
(2)
Ø 19.05
Ø 34.92
Ø 28.58
ߣߥߧߤऌ̧Ǯ
(3)
Ø 19.05
Ø 41.28
Ø 34.92
Size of the pipe connected to the outdoor unit (A)
Select the size of the pipe according to the below table.
Outdoor unit capacity
(kW)
(Cooling)
*Maximum pipe length within 90m
*Maximum pipe length over 90m
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
22.4 kW
Ø 9.52
Ø 19.05
Ø 15.88
Ø 12.70
Ø 19.05
Ø 15.88
ߤߤߧ̧Ǯड़ߤߪߣ̧Ǯ
Ø 22.22
Ø 19.05
Ø 22.22
Ø 19.05
ߤߪߤ̧Ǯड़ߥߥߨ̧Ǯ
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
ߥߥߩ̧Ǯड़ߦߢߢ̧Ǯ
Ø 22.22
Ø 22.22
ߦߢߣ̧Ǯड़ߦߧߢ̧Ǯ
ߦߧߣ̧Ǯड़ߧߢߦ̧Ǯ
Ø 15.88
Ø 19.05
ߧߢߧ̧Ǯड़ߧߨߢ̧Ǯ
Ø 28.58
Ø 28.58
ߧߨߣ̧Ǯड़ߨߥߥ̧Ǯ
ߨߥߦ̧Ǯड़ߩߢߥ̧Ǯ
Ø 34.92
Ø 34.92
ߩߢߦ̧Ǯड़߫ߪߦ̧Ǯ
Ø 19.05
Ø 22.22
߫ߪߧ̧Ǯड़ߣߥߧߤ̧Ǯ
Ø 41.28
Ø 34.92
Ø 41.28
Ø 34.92
ߣߥߧߥ̧Ǯड़ߣߨ߫ߢ̧Ǯ
ߣߨ߫ߣ̧Ǯड़ߤߧߤߢ̧Ǯ
Ø 22.22
Ø 53.98
Ø 53.98
Ø 25.40
note1)
Ø 53.98
Ø 53.98
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
࢜
For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
࢜
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe
installed on the site, a socket is provided by default together with the outdoor unit.