106
Setting the MCU and Pipe Addresses (for HR Only)
Setting the Pipe Addresses Manually
You can use the wired or wireless remote control or the S-NET Pro 2 to set the pipe addresses for each indoor unit.
Setting by using the wired or wireless remote control (For how to operate the remote
control buttons, see the remote control user manual.)
1. Turn on both the indoor unit and the remote control.
2. Enter the “Option setting mode” on the remote control.
3. Set the address of each MCU port that is connected to an indoor unit by referring to the following table.
(You can also set the address of each indoor unit.)
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Value
0
A: Address
setting mode
ߢࡑƟ˵ʪɇʒʒθʪϑϑͱ˙
the indoor unit
will not be set.
ߣࡑƟ˵ʪɇʒʒθʪϑϑͱ˙
the indoor unit
will be set.
ߢϩͱ߫ࡑ²Ї͝ʒθʪʒϑ
digit of the
indoor unit
address
ߢϩͱ߫ࡑƟʪ͝ϑʒ̈˝̈ϩ
of the indoor unit
address
ߢϩͱ߫ࡑƸ̈͝ϩϑʒ̈˝̈ϩ
of the indoor unit
address
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Value
1
0
ߢࡑƟ˵ʪŵđA
address will not
be set.
ߣࡑƟ˵ʪŵđA
address will be
set.
0
0 to F: RMC
group channel
0 to F: RMC
group address
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Value
2
0
ߢࡑƟ˵ʪđAƸ
address will not
be set.
ߣࡑƟ˵ʪđAƸ
address will be
set.
ߢϩͱߣࡑƟʪ͝ϑʒ̈˝̈ϩ
of the MCU
address
ߢϩͱ߫ࡑƸ̈͝ϩϑ
digit of the MCU
address
A to F: MCU port
address
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Value
3
0
0
0
0
0
Examples> If the indoor unit whose address is not yet set is connected to port A on the MCU 1, set 0A0000-
100000-20101A-300000.
If the indoor unit whose address is set to 9 is connected to port B on the MCU 2, set 0A1009-100000-
20102B-300000.
Setting by using S-NET Pro 2
ॷ
Set the pipe addresses by using Add-on > Change address on S-NET Pro 2. (For more information, see the
S-NET Pro 2 Help.)