Symptoms for abnormal operation of the 4way valve
ৄ
Abnormal noise during compressor operation, Increase in the suction temperature.
࢜
Symptoms for abnormal operation of the Main EEV
ৄ
It is not possible to control the superheat (SH)
ৄ
It is not possible to secure a DSH of higher than 20K
࢜
For more information, see the troubleshooting in the service manual.
࡛
If service valve (ball valve) check is required, corresponding outdoor unit will display the error.
࡛
If service valve (ball valve) check is required, auto detection mode will be terminated. Check service valve
(ball valve) of gas pipe and liquid pipe at the same time when checking service valve (ball valve).
࡛
When 4way valve, Main EEV detection is needed, run heating trial operation for more than 1 hour and
analyze the data to check for a problem.
࡛
If there's frost formed in outdoor unit or the outdoor unit is operating in defrost operation, it may be hard
to detect problem normally. In this case, perform Trial operation or Forced defrost operation to eliminate
the frost, and then perform Auto Trial Operation again.
࡛
If the operation range is not within guaranteed range, error may occur even though the product is normal.
࡛ƟͱθʪΧ̷ɇʀʪɇʀͱ͔Χͱ͝ʪ͝ϩͱθ̈͝ϑΧʪʀϩϩ˵ʪť9ࡥɵʪϑЇθʪϩͱʀЇϩͱ˙˙ϩ˵ʪΧͱиʪθϑЇΧΧ̷цѣθϑϩÃ˙̈͝ϑΧʪʀϩ̈ͱ͔͝Їϑϩɵʪ
performed with the power supply on, exercise extra care to prevent electric shock.