99
ENGLISH
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Silent mode
Main
0
7
0
0
Disabled (Factory default) Enables the silent mode for
night-time in cooling mode
(It operates automatically
depending on the
temperature.)
However, if the external
contact interface module
(MIM-B14) is used, entering
the silent mode is available
with contact signal in
cooling and heating mode.
(A type PBA : this function is
used in cooling mode.)
0
1
LEVEL 1 / Auto
0
2
LEVEL 2 / Auto
0
3
LEVEL 3 / Auto
0
4
LEVEL 1 / External contact
0
5
LEVEL 2 / External contact
0
6
LEVEL 3 / External contact
High-head
condition
setting
Main
0
8
0
0
Disabled (Factory default)
0
1
Level 1 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is
̷ͱʀɇϩʪʒߦߢड़ߪߢ͔ɇɵͱЭʪϩ˵ʪ
indoor unit
0
2
Level 2 of height difference
type 1 (Indoor unit is lower
than outdoor unit)
When outdoor unit is
located over 80m above the
indoor unit
0
3
Height difference type 2
(Outdoor unit is lower than
indoor unit)
When indoor unit is over 30
m above the outdoor unit
Long-piping
condition
setting (Setting
is unnecessary
if high-head
condition is set)
Main
0
9
0
0
Disabled (Factory default)
0
1
LEVEL 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
ߣߢߢड़ߣߩߢ͔
0
2
LEVEL 2
When equivalent length of
farthest indoor unit from
the outdoor unit is over
170m
Energy saving
setting
(A Type PBA)
Main
1
0
0
0
Disabled (Factory default)
0
1
Enabled
Energy saving mode
triggers when the room
temperature reaches
desired temperature while
operating in heating mode.
Energy control
operation
(B Type PBA)
Main
1
0
0
0
Basic (Factory default)
Energy control option
of designated operation
sequence
࢜
Operating in energy
saving mode, capacity
might decrease
compared to normal
operation mode
0
1
Energy saving
0
2
Power
Rotation defrost
(HR only)
Main
1
1
0
0
Disabled (Factory default)
0
1
Enabled
When enabled, continuous
heating operation is
possible but heating
performance will decrease
during rotation defrost
operation