9
Installation Pr
oc
edur
e
English
Spacing requirements
2500 mm or more
1500 mm or more
17 mm
20 mm
A
Obstruction
(Unit: mm)
Model
AG060AN4DKH
AG072AN4DKH
AG090AN4DKH
AG105AN4DKH
A
251
293
C
C: 1500 mm or more
C
C
C
NOTE
• The shape of the fan coil unit may differ depending
on the model.
• The recommended ceiling height is 2.7m.
CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit. The components
of the indoor unit must be reachable and removable
under safe conditions for people and the unit.
• Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
• You must hold the hanger plate on the corner and
carry the indoor unit.
Step 3 Optional: Insulating the body
of the indoor unit
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C and humidity is over
80%, you must apply an extra 10 mm thick polyethylene
insulation or a similar type of insulation to the body of
the indoor unit.
Cut away the part where pipes are pulled out for the
insulating work.
A
D
E
B
C
Insulate the end of the pipe and some curved area by
using separate insulator.
NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as
the reference for its outer circumference.)
(Unit: mm)
Indoor unit
A
B
C
D
E
4 way Cassette <S>
(840x204x840)
AG060AN4DKH
AG072AN4DKH 910X151 940X151 610X151 650X151 870X870
4 way Cassette <M>
(840x246x840)
AG090AN4DKH
AG105AN4DKH 910X193 940X193 610X193 650X193 870X870