32
Installation Procedure
Installation Pr
oc
edur
e
English
• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically to "Use + 3 minute delay."
• If you set the Maximum filter usage time (SEG18) option to value other than 2 and 6, it is automatically set to
2(1000 hours).
• If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
• The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don't need to set the SEG5
option additionally. Note that even if the central control system is not connected, no errors occur. If you want a
specific fan coil unit not to be controlled by the central control system, set the SEG option of that fan coil unit to 0
(Disuse).
• The external heater output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of AIM-B14)
Installation options for the 02 series (detailed)
Option No.: : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Evaporator Drying
(*8)
Use of external temperature sensor /
Minimizing fan operation when thermostat
is off
Use of central
control
Compensation of the fan
RPM
Indications
and details
Indication Detail Indication Detail Indication Detail Indication
Detail
Indication Detail Indication
Detail
Use of
external
temperature
sensor
Minimizing fan
operation when
thermostat is off
0
2
0
Disuse
0
Disuse
Disuse
0
Disuse
0
Disuse
1
Use
Disuse
2
Disuse
(Heating) Use (* 1)
2
Use
(5min)
3
Use
(Heating) Use (* 1)
1
Compensation
of the fan RPM
4
Disuse
(Cooling) Use (* 1)
5
Use
(Cooling) Use (* 1)
4
Use
(10min)
6
Disuse
Use (* 1)
1
Use
7
Use
Use (* 1)
8
Disuse
(Cooling) Lowest
fan speed (* 1)
2
(4 way only)
High-ceiling
mode
6
Use
(30min)
9
Use
(Cooling) Lowest
fan speed (* 1)
A
Disuse
(Cooling) Lowest
fan speed /
(Heating) Use (* 1)
B
Use
(Cooling) Lowest
fan speed /
(Heating) Use (* 1)