Installation Procedure
Installation Pr
oc
edur
e
English
2-2
Insulate the piping.
• Incorrect piping insulation may cause
condensation on the piping surfaces or degrade
the product performance.
• Make sure that the bent parts of the piping are
correctly covered with insulation.
Fix firmly so that there is no gap.
Insulation
Fan coil unit
Be sure to overlap the insulation.
Insulation
Clamp
Pipe
Pipe
Insulation
Short piping system
• You can use joined insulation (joining the pipes
and insulating them together), but avoid excessive
pressing.
• When joined insulation is used, apply the insulation
thickness one step higher.
Insulation
Water pipe
CAUTION
• Make sure that the pipe insulation is free of gaps and
cracks, and apply adhesives specific to the insulation
joints so that moisture cannot enter through them.
• If the pipe insulation is exposed to the sun's
ultraviolet rays, wind tape around the insulated pipe
as a finishing work.
(When winding tape, be careful not to reduce the
thickness of insulation.)
• Be careful not to reduce the thickness of the
insulation at the bent parts of the pipe, the pipe
hanger, etc.
• If the thickness of insulation is reduced, apply
additional insulation to compensate the thickness.
Pipe insulation
a x 3
Hanger
Additional insulation
a
Step 8 Installing the water pipes
1
Remove the caps from the water pipe inlet and outlet.
OUT
(water pipe outlet)
Air vent valve
IN
(water pipe inlet)
2
Be sure to check the positions of the water pipe inlet
and outlet of the fan coil unit by finding their labels
(IN and OUT) attached.
• The water pipe inlet label is printed with IN and
the water pipe outlet label with OUT.
• Note that the air vent valve is attached to the side
where you can find the water pipe outlet.
IN (inlet)
OUT (outlet)