(*1) Minimizing fan operation when thermostat is off:
–
The fan operates for 20 seconds at an interval of 5 minutes in the
Heat
mode.
–
When thermostat is off in the
Cool
mode, the fan stops or Ultra breeze function starts based on the
setting.
(*2) 1: The fan is turned on continually when the hot water heater is turned on,
3: The fan is turned off when the hot water heater is turned on with cooling only fan coil unit.
(*3) When the following 2 or 3 is used as external heater On or Off signal, the signal for monitoring external
contact control will not be output.
2 : The fan is turned on continually when the external heater is turned on
3 : The fan is turned off when the external heater is turned on with cooling only fan coil unit
※ If the fan is set to off for cooling only fan coil unit by setting the SEG9=3 or SEG15=3, you need to use an
external sensor or wired remote control sensor to detect indoor temperature exactly.
(* 4) Output occurs when operating in the
Cool
or
Dry
mode.
(* 5) An Economizer controller is required to use the Cooling output by external equipment function.
(* 6) Default setting : 5 ℃
(*7) This function is only applicable for the 4 way cassettes. If the fan coil unit operates in the
Heat
mode
immediately after finishing the cooling operation, the condensated water in the drain pan becomes water
steam by the heat of the fan coil unit heat exchanger. Since the water steam might be condensed on the fan
coil unit, which may fall into a living space, use this function to remove the water steam out of the fan coil
unit by operating the fan (for maximum 20 minutes) although the fan coil unit is turned off after the
Cool
mode is turned to the
Heat
mode.
(*8) When you turn off the
Cool
or
Dry
mode, the indoor unit fan automatically operates for the set time and then
stops.
(*9)
Soft Off
: If no motion is detected for the Soft Off time, the MDS Kit turns off the indoor units.
Then if any motion is detected until the Hard Off time is passed, the MDS Kit restarts the indoor
units.
(*10)
Hard Off
: If no motion is detected for the Hard Off time, the Mds Kit turns hard off the indoor units.
Then although any motion is detected, the MDS Kit does not restart the indoor and outdoor units.
You must manually resttart the units with the wired of wireless remote control.
Installation options for the 05 series
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
-
-
-
-
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
-
-
-
-
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
Adjustable breeze Water valve control
type
Valve control at
Thermo Off
Water pipe valve is
installed?
Control variable
when using hot
water heater or
external heater
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Choose whether
to use Interface
module
Displaying the
water-temperature
rise-prevention
error messages
Timing separation
of the cooling and
heating signals for
the water pipe valve
Forced air speed for
cooling / heating
-