3-10
Samsung Electronics
Operating Instructions and Installation
3-2-2(f) Flare Modification
Flare modification procedure
1 ) Cut the pipe using a pipe cutter.
• Tools used
2 ) Remove burrs at the tip of the pipe cut.
C a u t i o n : Burrs not removed may result in
leakage of gas.
3 ) Insert a flare nut into the pipe and modifty flare .
* Unproper flaring
Outer diameter
A(mm)
ø6.35mm
1.3
ø9.52mm
1.8
ø12.7mm
2.0
Oblique
90°
Raughness
Burr
Pipe
Reamer
Inclined
Surface
damaged
Cracked
Uneven
thickness
D
A