EB 8389S EN
47
Statistical information
−
Much higher over section:
[ ], , ,
−
Much lower over section:
[ ], , ,
2.
Diagnosis > Statistical information > Drive
signal diagram > Hysteresis
−
Tolerance band of hysteresis: 1 to 5 %, [5 %]
3.
−
Enable time distance:
[User-defined], Immediately
−
Min. time distance from test: 1 to 24 h, [1 h]
4.
−
Start test.
Note:
Cancel the test by right-clicking 'Stop
test' and selecting 'Execute' or by
pressing the rotary pushbutton at the
positioner.
3.7.1
Analysis and monitoring
The test is monitored by the 'Tolerance band
of hysteresis' parameter:
−
If the valve position x leaves the 'Toler-
ance band of hysteresis' during the test,
the test is immediately canceled and the
positioner returns to closed-loop opera-
tion.
−
If a change in set point (∆w) occurs
which is greater than the 'Tolerance band
of hysteresis', the test is immediately can-
celed and the test is started again after
waiting 30 seconds using the new oper-
ating point.
If this test is also canceled by a change
in set point (
∆w)
, it is reactivated after
waiting 60 seconds using the new oper-
ating point.
The test is started again ten times at the
maximum. The time between tests is in-
creased by 30 seconds each time (30 s x
Number of tests repeated). After the test
is canceled for the tenth time, the time
entered in 'Min. time distance from test'
is kept again.
If the analysis of the hysteresis pinpoints
'Friction' or 'External leakage', the positioner
generates a corresponding status message.
Diagnosis > Status messages > Extended
−
Friction: , , ,
Note:
The results from the Statistical infor-
mation test can be checked by per-
forming a test from Tests (out-of-ser-
vice diagnostics) if the process allows
it. See
u
Section 4.2.
3.7.2
Resetting single status
messages
The messages 'Friction' and 'External leak-
age' are reset by the command "Reset 'Drive
signal diagram hysteresis" or "Reset 'Drive
signal diagram hysteresis - short-term".
By selecting and executing the command
"Reset 'Drive signal diagram hysteresis", all
the measured data of the diagram, including
the short-term monitoring, are reset.
By selecting and executing the command
"Reset 'Drive signal diagram hysteresis -
Содержание TROVIS SAFE 3731 Series
Страница 5: ...EB 8389S EN 5...
Страница 49: ......
Страница 73: ...EB 8389S EN 73...
Страница 83: ...EB 8389S EN 83 Binary input...
Страница 101: ...EB 8389S EN 101...
Страница 102: ...102 EB 8389S EN...