56
EB 8389S EN
Tests
1.
Settings > Identification > Positioner >
Actuator
−
Model:
Single acting
, [-/-]
2.
−
Booster:
Not present
, [-/-]
Defining parameters
1. Switch to manual mode.
2.
Select classification for status messages.
3. Start test.
The 'Test information' status indicates
'Running test'. 'd1' and 'tEST' are indi-
cated in alternating sequence on the po-
sitioner display.
'Function check' is activated as the
condensed state.
1.
Operation > Operating mode
1)
Target mode (Code 0): Manual
2.
Settings > Positioner > Error control >
Classification report > Extended > ...
Air supply
−
Perhaps modified (TEST):
[ ], , ,
−
Perhaps not enough (TEST):
[ ], , ,
−
Working at full capacity (TEST):
[ ], , ,
Leakage pneumatics
−
Perhaps existing (TEST):
[ ], , ,
−
Perhaps too large (TEST):
[ ], , ,
Actuator springs
−
Perhaps spring stiffness reduced (TEST)
[ ], , ,
−
Perhaps bias reduced (TEST):
[ ], , ,
−
Working at full capacity (TEST):
[ ], , ,
3. Start test
Note:
Cancel the test by right-clicking 'Stop
test' and selecting 'Execute' or by
pressing the rotary pushbutton at the
positioner.
After the test has been canceled, the posi-
tioner remains in manual mode.
In TROVIS-VIEW the test information and
progress flag of the test are displayed. The
'Test information' status indicates 'Test fin
-
ished' after the test is finished.
Note:
Every time the test is performed, old
measured data are overwritten (Rep-
etition).
4.1.1
Analysis and monitoring
The following effects can be read by com-
paring the correlation between the drive sig-
nal and valve position measured during the
test and in the reference graph: