EB 8389S EN
11
Description
2.
Tests (out-of-service diagnostics)
Similar to the statistical information func-
tion, data are compiled, saved and ana-
lyzed by the positioner. However, in this
case, the valve position is not determined
by the set point, but by the active test.
NOTICE
The tests can only be started when
the conditions in the plant allow it
(e.g. plant shutdown or service work
in the workshop). For reasons of
safety, these tests, except for partial
stroke testing, can only be performed
in the manual mode.
An active test is stopped and the posi-
tioner changes to the fail-safe position
when the electrical signal falls below a
certain level or when the solenoid valve
is triggered or the forced venting func-
tion is activated.
1.3.1
Application type
Different diagnostic functions are available
depending on the application type selected
in EXPERTplus.
Depending on the application type selected,
the positioner behaves differently in the au-
tomatic mode:
−
Control valve
The positioner uses the set point to posi-
tion the valve.
The valve position (current position) ap-
pears in % on the display.
−
Open/close (on/off) valve
Discrete analysis of the set point
The valve position (current position) in %
and O/C (Open/Close) appear in alter-
nating sequence on the display. See
u
Section 3.1.
1.3.2
Analysis
Table 2 shows the diagnostic functions and
their statements on the condition of the valve
depending on the application type.