EB 8389S EN
71
Tests
−
'Rise time' [s]
−
'Settling time' [s]
Analysis of measured data (ramp test):
−
'Overshoot' (relative to the step height)
[%]
The results of the first partial stroke test are
used as the reference measurement.
Note:
Changes in the diagnostic parame-
ters listed below affect the test. The
results of the next following partial
stroke test are used as the new refer-
ence measurement:
−
'Step start'
−
'Step end'
−
'Activation of the ramp function'
−
'Ramp time (rising)'
−
'Ramp time (falling)'
−
'Delay time after step'
Test not completed
If the test was not completed, the reason for
cancelation is indicated in the corresponding
reading by the 'Maintenance alarm' mes-
sage. The positioner generates a 'PST/FST'
message with the selected status classifica
-
tion. 'Extended diagnosis' (Code 79) is acti-
vated regardless of the status classification.
Diagnosis > Status messages > Extended
PST/FST: , , , ,
Note:
The 'No test available' status remains
active until a partial stroke test is
completed successfully.
4.4.4
Resetting single status
messages
The diagnostic parameters and measured
data analysis of the partial stroke test are re-
set by selecting and executing the command
'Reset PST'.
The positioner saves the measured data
analysis of the last three partial stroke tests.
The analysis of the penultimate test is deleted
when another test is performed.
Diagnosis > Status messages > Reset
−
Reset PST
4.4.5
Step response
The dynamic performance of the control
valve can be tested by plotting its step re-
sponse.
The step response of the valve is recorded by
performing the partial stroke test with sud-
den changes in the valve position.
In addition, the following settings are recom-
mended:
−
Deactivate all cancelation conditions of
the partial stroke test, providing the pro-
cess allows it.
Содержание TROVIS SAFE 3731 Series
Страница 5: ...EB 8389S EN 5...
Страница 49: ......
Страница 73: ...EB 8389S EN 73...
Страница 83: ...EB 8389S EN 83 Binary input...
Страница 101: ...EB 8389S EN 101...
Страница 102: ...102 EB 8389S EN...