EB 6493 EN
5-3
Installation
5.4 Electrical connection
Risk of fatal injury due to electric shock.
Î
For electrical installation, you are re
-
quired to observe the relevant electro
-
technical regulations of the country of
use as well as the regulations of the local
power suppliers.
Therefore, such work must be performed by
trained and experienced personnel.
Î
Do not connect ELV cables (according to
VDE 0100) to these terminals.
Î
Before performing any work on the ter
-
minals, disconnect the voltage supply
from the compact controller.
Notes on electric wiring
Î
Install the power supply lines and the sig-
nal lines separately. Do not install them
parallel to each other.
Î
To improve noise immunity, observe a
minimum distance of 10 cm between the
power line and the measuring input line.
Î
To avoid measurement errors or other
disturbances, use shielded cables for the
analog and binary signal lines. Ground
the shield at one side, either at the con-
trol cabinet inlet or outlet, using the larg-
est possible cross-section.
Î
Connect the central grounding point and
the PE grounding conductor with a cable
with 10 mm² wire cross-section using the
shortest route.
DANGER
!
Î
Inductances in the control cabinet, e.g.
contactor coils, must be equipped with
suitable interference suppressors (RC ele
-
ments).
Î
Control cabinet elements with high field
strength, e.g. transformers or frequency
converters, must be shielded with sepa-
rators providing a good ground connec-
tion.
The compact controller has plug-on screw
terminals for lines with a wire cross-section
from 0.5 to 1.5 mm². The lines are connect
-
ed to the terminal strips 1 to 2 (see Fig. 5-2).
Î
Plug the plug-on screw terminals securely
into the appropriate connector sockets in
the controller.
Note on analog inputs
Î
When resistance thermometers are con-
nected in two-wire circuits, connect a
jumper to the controller terminals (see
The lead resistance can reach several ohms
over long distances, causing the measured
value to be considerably distorted. This can
be compensated for by a correction value
(see '-CO- F.FOR Feedforward control' in the
Configuration Manual
u
Note
Содержание Trovis 6493
Страница 6: ...Contents EB 6493 EN...
Страница 22: ...3 10 EB 6493 EN...
Страница 30: ...5 6 EB 6493 EN...
Страница 36: ...6 6 EB 6493 EN...
Страница 72: ...8 12 EB 6493 EN...
Страница 84: ...11 2 EB 6493 EN...
Страница 86: ...12 2 EB 6493 EN...
Страница 88: ...13 2 EB 6493 EN...
Страница 90: ...14 2 EB 6493 EN...
Страница 92: ...15 2 EB 6493 EN...
Страница 95: ...EB 6493 EN 16 3 Certificates TR CU certificate...
Страница 96: ...16 4 EB 6493 EN Certificates...
Страница 97: ...EB 6493 EN 16 5 Certificates...
Страница 98: ...16 6 EB 6493 EN...
Страница 125: ......
Страница 126: ......
Страница 127: ......