![Samson Trovis 6493 Скачать руководство пользователя страница 111](http://html1.mh-extra.com/html/samson/trovis-6493/trovis-6493_mounting-and-operating-instructions_4073788111.webp)
EB 6493 EN
17-13
Annex A (configuration guide)
…
……………
or
……………………………………
………………… ……………………………
or
……………………
and
, followed by
Menu Function -CO-
Setting
options
1)
Description of functions
Parameter level -PA-
Parameter
selection
Parameter name
Value range
1)
OUT
Y.SRC
Source for analog
output Y
on Y.PID
on Y.X
on Y.WE
on Y.XD
Output YPID
Input X
Input WE
Error XD
noPA Y.SRC/Y.PID
noPA Y.SRC/Y.X
noPA Y.SRC/Y.WE
noPA Y.SRC/Y.XD
No
parameters
CALC
Mathematical
adaptation analog
output Y
oFF CA.Y
on CA.Y
POS CA.Y
nE6 CA.Y
OFF (no output signal)
Without condition
With positive sign
With negative sign
CALC/CA.Y
CALC/CA.Y
CALC/CA.Y
CA.K1
CA.K2
CA.K3
Constant 1
Constant 2
Constant 3
[
0.0
… 100.0 %]
[0.0 …
1.0
… 10.0]
[–10.0 …
0.0
… +110.0 %]
C.OUT
On/off or three-step
output
oFF 2/3.S
OFF
C.OUT/2/3.STP
on 2.STP
i.Fb 3.STP
On/off output
Three-step output with internal
feedback
C.OUT/2.STP
C.OUT/3.STP
KPL1
KPL2
TYL1
Gain Y+ (BO1)
Gain Y– (BO2)
Cycle duration Y+ (BO1)
[0.1 …
1.0
… 100.0]
[0.1 …
1.0
… 100.0]
[1.0 …
10.0
… 9999 s]
E.Fb 3.STP Three-step output with external
feedback
C.OUT/3.STP
TYL2
TYL1
Cycle duration Y– (BO2)
Min. duty cycle Y+ (BO1)
[1.0 …
10.0
… 9999 s]
[0.1 …
1.0 s
… TYL1]
PP 2.STP
i.PP 3.STP
On/off output with PPM
Three-step output with internal
feedback and PPM
C.OUT/2.STP
C.OUT/3.STP
TYL2
XSDY
Surcharge
Min. duty cycle Y– (BO2)
Hysteresis
Dead band
[0.1 …
1.0 s
… TYL2]
[0.10 …
0.50 %
… TZ]
[XSDY …
2.00
… 100 %]
E.PP 3.STP Three-step output with external
feedback and PPM
C.OUT/3.STP
TY
Transit time
[1 …
60
… 9999 s]
B.OUT
Binary output BO1
oFF B.BO1
F01 B.BO1
F02 B.BO1
F03 B.BO1
OFF
Active when binary input is set
Active when WE is active
Active in automatic mode
noPA B.OUT/B.BO1
No parameter
Binary output BO1
oFF B.BO2
F01 B.BO2
F02 B.BO2
F03 B.BO2
OFF
Active when binary input is set
Active when WE is active
Active in automatic mode
noPA B.OUT1/B.BO2
No parameter
1)
Default setting is in
bold
print.
1)
Default setting is in
bold
print.
Содержание Trovis 6493
Страница 6: ...Contents EB 6493 EN...
Страница 22: ...3 10 EB 6493 EN...
Страница 30: ...5 6 EB 6493 EN...
Страница 36: ...6 6 EB 6493 EN...
Страница 72: ...8 12 EB 6493 EN...
Страница 84: ...11 2 EB 6493 EN...
Страница 86: ...12 2 EB 6493 EN...
Страница 88: ...13 2 EB 6493 EN...
Страница 90: ...14 2 EB 6493 EN...
Страница 92: ...15 2 EB 6493 EN...
Страница 95: ...EB 6493 EN 16 3 Certificates TR CU certificate...
Страница 96: ...16 4 EB 6493 EN Certificates...
Страница 97: ...EB 6493 EN 16 5 Certificates...
Страница 98: ...16 6 EB 6493 EN...
Страница 125: ......
Страница 126: ......
Страница 127: ......