Activate editing mode for times-of-use.
Display:
1–7
Select period/day for which the times-of-use are to
be valid:
1–7 = every day,
1 = Monday, 2 = Tuesday, ..., 7 = Sunday
Activate editing mode for period/day.
Display shows:
START
;
blinks
Edit start time (steps of 30 minutes).
Confirm start time. Display shows:
STOP
Edit stop time (steps of 30 minutes).
Confirm stop time.
Display shows:
START
The second time-of-use is set like the first time-of-use.
To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.
Select
End
on the display.
Exit the datapoint for times-of-use.
Exit the parameter level.
Return to the operating level.
Note!
Do not use the 1–7 datapoints to check the programmed times-of-use. Otherwise, the
times-of-use are reset to their default settings.
Note!
The controller automatically returns to the operating level if the keys are left unpressed for two
minutes.
14
EB 5179 EN
Operation
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
STOP
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...