Function block parameters Co4
Limitation factor (Fb02 = ON)
0 to 25.5
Activate priority in case of deviation
(Fb06 = ON)
0 to 30 °C
Day of week (Fb08 = ON)
0, 1 to 7
Disinfection temperature (Fb08 = ON)
60 to 90 °C
Boost of charging temperature
0 to 30 °C
Start – Stop (Fb08 = ON)
00:00 to 23:30
T
Y
(valve transit time) (Fb09 = ON)
15 to 240 s
K
P
(proportional gain) (Fb09/14 = ON)
0.1 to 50
T
N
(reset time) (Fb09/14 = ON)
1 to 999 s
T
V
(derivative-action time) (Fb14 = ON)
0 to 999 s
Data for heating circuits (Fb12 = ON)
1 to 3
Max. system deviation (Fb13 = ON)
2 to 10 °C
PA5: System-wide parameters
Parameters
PA5
Range of values
Gradient, return flow
0.4 to 3.2
Level, return flow
–30 to 30 °C
Maximum return flow temperature
20 to 90 °C
Minimum return flow temperature
20 to 90 °C
Maximum capacity of entire system
0.1 to 5999 kW
Maximum capacity of heating
0.1 to 5999 kW
Maximum capacity of DHW heating
0.1 to 5999 kW
Proport.-action coefficient for limitation
0.1 to 10
Maximum flow rate of entire system
0.01 to 99.9 m
3
/h
Maximum flow rate of heating
0.01 to 99.9 m
3
/h
Maximum flow rate of DHW heating
0.01 to 99.9 m
3
/h
Minimum flow rate
0.01 to 99.9 m
3
/h
Proport.-action coefficient for limitation
0.1 to 10
Outdoor temperature, point 1
–30 to 90 °C
Outdoor temperature, point 2
–30 to 90 °C
EB 5179 EN
135
Appendix
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...