Co8: Error initialization
Fb Function
WE
Anl
Comments
Function block parameters
/ Range of values (default setting)
00 Dial-up also upon
corrected fault
OFF
All
CO8 -> Fb00 = ON: Dial-up to the building control station
both when a fault was detected and a fault was corrected
CO8 -> Fb00 = OFF: Dial-up to building control station only
when fault was detected
01
to
17
BE1 in FSr
to
BE 17 in FSr
OFF
All
Co8 -> Fb01 to Fb17 = ON:
Option:
Rising signal edge/make contact
Negative signal edge/break contact
Note:
Can only be changed after entering key number
22 Limit monitoring
OFF
All
Configurable over Modbus
23 Alarm binary input
changed
OFF
All
Co8 -> Fb23 = ON: Subsequent faults reported in error status
register (bit D11)
Fb Function block, WE Default setting
Co9: Modbus and meter bus communication
FB Function
WE
Comments
Function block parameters
/ Range of values (default setting)
00 Modbus
ON CO9 -> FB00 = ON: Modbus active
01 Modem
OFF CO9 -> FB01 = ON: Modem active
02 Modem dialing
mode
OFF CO9 -> FB02 = ON: Pulse dialing
CO9 -> FB02 = OFF: Tone dialing
03 Lock dial-up
OFF CO9 -> FB03 = ON: No dial-up in case of fault
04 Modbus 16-bit
addressing
OFF CO9 -> Fb04 = ON: 16-bit addressing
CO9 -> Fb04 = OFF: 8-bit addressing
05 Reserved
06 Text message alarm OFF CO9 -> FB06 = ON: Fault alarm sent to mobile phone
07 Text message
dialing mode
OFF CO9 -> FB07 = ON: Pulse dialing
CO9 -> FB07 = OFF: Tone dialing
10 Fax alarm
OFF CO9 -> FB10 = ON: Alarm sent to fax
11 Fax dialing mode
OFF CO9 -> FB11 = ON: Pulse dialing
CO9 -> FB11 = OFF: Tone dialing
EB 5179 EN
105
Appendix
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...