PA1 to PA3: Heating circuits HK1 to HK3
Parameters
PA1
PA2
PA3
Range of values
Gradient, flow
0.4 to 3.2
Level, flow
–30 to 30 °C
Maximum flow temperature
20 to 130 °C
Minimum flow temperature
20 to 130 °C
Set-back difference
0 to 50 °C
Gradient, return flow
0.4 to 3.2
Level, return flow
–30 to 30 °C
Outdoor temperature; point 1
–30 to 90 °C
Outdoor temperature; point 2
–30 to 90 °C
Outdoor temperature; point 3
–30 to 90 °C
Outdoor temperature; point 4
–30 to 90 °C
Flow temperature; point 1
20 to 130 °C
Flow temperature; point 2
20 to 130 °C
Flow temperature; point 3
20 to 130 °C
Flow temperature; point 4
20 to 130 °C
Return flow temperature; point 1
20 to 90 °C
Return flow temperature; point 2
20 to 90 °C
Return flow temperature; point 3
20 to 90 °C
Return flow temperature; point 4
20 to 90 °C
Set-back temperature; point 2
0 to 50 °C
Set-back temperature; point 3
0 to 50 °C
Day set point
10 to 90 °C
Night set point
10 to 90 °C
Sustained temperature
10 to 90 °C
Maximum return flow temperature
20 to 90 °C
Minimum return flow temperature
20 to 90 °C
OT activation value rated operation
–30 to 50 °C
OT deactivation value
reduced operation
–10 to 50 °C
OT deactivation value
rated operation
0 to 90 °C
EB 5179 EN
131
Appendix
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...