Co6: Sensor initialization
Fb Function
WE
Anl
Comments
Function block parameters
/ Range of values (default setting)
00 Sensor selection
general
ON
All
Co6 -> Fb00 = ON: Pt 100; Pt 1000
Co6 -> Fb00 = OFF: Pt 100; PTC
01
to
17
Sensor input 1
to
sensor input 17
OFF
All
Any sensor inputs that are different from the settings for
function block Fb00
Co6 -> Fb01 to Fb17 = ON:
select:
Outdoor temperature input:
0/4 to 20 mA, 0 to 10 V = –40 to 50 °C
Other temperature inputs:
0/4 to 20 mA, 0 to 10 V = 0 to 160 °C
Ni200, Ni1000, PTC, NTC, Pt1000, Pt100, 0/4-20, 0-10
23 Sensor calibration
OFF
All
Fb Function block, WE Default setting
Co7: LON communication
Fb Function
WE Anl
Comments
Function block parameters
/ Range of values (default setting)
00 LON active
OFF All Co7 -> Fb00 = ON: LON interface active
01 Controller as
master controller
OFF All Co7 -> Fb01 = ON: Controller is defined as primary controller
(processes the external demand as master controller)
Co7 -> Fb01 = OFF: Controller is defined as secondary
controller
02 Controller time
OFF All Co7 -> Fb02 = ON: Controller time = LON system time
03 Outdoor
temperature 1
OFF All Co7 -> Fb03 = ON: LON outdoor temperature 1
Select:
Terminal number of outdoor sensor
04 Outdoor
temperature 2
OFF All Co7 -> Fb04 = ON: LON outdoor temperature 2
Select:
Terminal number of outdoor sensor
05 Report operational
faults of other LON
participants
OFF All Co7 -> Fb05 = ON: Report fault alarms of other LON
participants
Fb Function block, WE Default setting
104
EB 5179 EN
Appendix
Содержание TROVIS 5179
Страница 87: ...EB 5179 EN 87 Communication...
Страница 93: ...EB 5179 EN 93 System Anl 3 Option Type 5244 Type 5257 5 System Anl 4 Option Type 5244 Type 5257 5...
Страница 94: ...94 EB 5179 EN System Anl 5 Option Type 5244 Type 5257 5 System Anl 6 Option Type 5244 Type 5257 5...
Страница 95: ...EB 5179 EN 95 _ _ _ 3 1 2 System Anl 8 Option Type 5244 Type 5257 5 System Anl 7 Option Type 5244 Type 5257 5...
Страница 103: ...Fb Function WE Anl Comments Function block parameters Range of values default setting...