36
EB 7500 EN
Technical data
Type 3424-2 ...
Additional Module
1)
i/p converter, 4 to 20 mA or 0 to 20 mA input, 0.2 to 1 bar (3 to 15 psi) output
Input impedance approx. 200 Ω and 4 mH
Type 3424-4
Manual/automatic transfer
Input: 0.2 to 1.0 bar (3 to 15 psi)
Output: 0.2 to 1.0 bar (3 to 15 psi), max. 0.02 to 1.35 bar (0.3 to 19 psi)
Type 3424-5
Control mode changeover · Output: switching pressure approx. 1.4 bar (only for
Types 3423-2/-3)
Type 3424-6
Signal limiter for yA, R or w · Limitation adjustable between 0.2 and 1.0 bar (3 and 15 psi)
Supply air
Supply air 1.4 ±0.1 bar (20 ±1.5 psi) · Air consumption per unit
<
0.15 m
n
³/h
Medium for supply
air and inputs
Instrument air, free from corrosive substances
Air quality acc. to
ISO 8573-1: 2001
Max. particle size and density: Class 3 · Oil content: Class 2 · Pressure dew point: Class 3 or
at least 10 K below the lowest ambient temperature to be expected
Permissible ambient
temperature range
–20 to +60 °C
Compliance
·
Weight (approx.)
Manual control station (without components): 2.5 kg · Type 3421 with controller module:
3.2 kg
Type 3421 Controller with controller or additional module: 3.6 kg
1)
No longer available
Technical data for the devices can be found in the following data sheets:
Device designation (Type)
Further details in data sheet
Type 3421
Pneumatic Compact Controller
u
T 7506
Type 3422
Manual Control Station
u
T 7506
Type 3427
Manual Control Station
u
T 7511
Type 3425
Pneumatic Controller (wall-mounted and field
controller)
u
T 7512
Type 3416
Indicator
u
T 7526
Type 3417
Pneumatic Control Unit
u
T 7527
Types 3423-1/-2/-3/-4/-5/-6/-7/-9
Controller
Modules
u
T 7521
Types 3424-4/-5/-6
Additional Modules
u
T 7524
Type 3424-2
Additional Module
u
T 7523