Conversion
9.3 Checking the controller
function
To check the controller, the controlled vari-
able
x
and the output
y
must be bypassed at
ports
x
and
y
on the controller station.
Perform the following settings:
−
Turnboard
A
to increasing/decreasing >
<,
−
Fully open Tn restriction (0.03 min),
−
Fully close Tv restriction (0.01 min).
Î
Turn the set point rotary knob to change
the reference variable through its whole
range.
The controlled variable pointer (red) and
the output reading (small dial) follow the
reference variable over the whole range
when the controller functions properly.