EB 7500 EN
31
Conversion
ative amplifier (14) in place. Unscrew
cover plate (11.1) and mount Tv restrictor
(11).
PI to PID:
Same as for P to PD.
P to PID:
Same as for P to PD. In addi-
tion, replace adjuster (12) with Tn restric-
tor (10).
P controller with set-point-dependent op-
erating point: Attach plate with restriction
(15) in place of the adjuster for operat-
ing point (12).
We recommend replacing old O-rings with
new ones as well as replacing the filter in the
restriction (7 in Fig. 1 and Fig. 19).
Note
P to PI
P to P/PI
Fig. 19:
Changing the controller function
Filter
Restriction (7)