EB 7500 EN
23
Design and principle of operation
5.8 Optional electrical limit
contacts
The listed limit contacts and LEDs are no lon
-
ger available.
The limit contacts indicate when the con-
trolled variable x falls below and/or exceeds
an adjustable limit.
The version with
inductive limit contacts
has
a controlled variable pointer fitted with metal
tags which move adjustable proximity
switches within a magnetic field.
The operation of the inductive limit contacts
requires switching amplifiers in accordance
with EN 60947-5-6 to be connected in the
output circuit.
The corresponding wiring (Fig. 17) allows
the limit contacts to be additionally fitted
with LEDs.
Internal electrical limit contacts with LED are
amplified on the internal board and only
used to actuate LEDs. These contacts require
a 24 V DC power supply.
See section 3.2 on how to adjust the limit
contacts.