- Type SAM-01 to SAM-11 Linear Actuators -
The travel limit switches
WE-S3
and
WE-S6
are mounted on the lateral mounting plate.
They are operated via the operating cams lo-
cated at the top end of the actuator stem.
Depending on the movement of the actuator
stem "OPEN"/"CLOSED", the associated
limit switch deactivates the actuator travel.
You can adjust the switching position at ran-
dom by moving the respective switch axially
over the oblong hole, retighten.
WE-S3
– Move actuator stem to final position ma-
nually ("OPEN") - actuator stem retracted -.
First, the switch
WE-S3
must be above from
the operating cam.
WE-S6
– Move actuator stem to final position ma-
nually ("CLOSED") - actuator stem re-
tracted -.
First, the switch
WE-S6
must be below the
operating cam.
For both cases ...
– Loosen the mounting screws of the respec-
tive s witch from the back s ide s o that the
switch may be operated.
– Push the switch up/down until the operating
cams switch off the actuator - depending on
the travel - (check with a gauge).
– Retighten mounting screws.
Check switching position in a test run.
S3
S6
"OPEN"
Actuator stem
"CLOSED"
Fig. 20
⋅
Operating cams WE-S3/WE-S6
&+#&,