![Samson Media 7 Скачать руководство пользователя страница 78](http://html.mh-extra.com/html/samson/media-7/media-7_mounting-and-operating-instructions_805914078.webp)
78
EB 9510 EN
Annex
Menu
Adjustment range/values/description
Slot 1
2.4.2
The available parameters of inserted options modules are
listed depending on the optional additional function.
Slot 2
2.4.3
Slot 3
2.4.4
Slot 4
2.4.5
AO: Analog output option
Option module
identification
... .1
Detection of optional additional function: AO: Analog output
Option module status
... .2
Read the current status of the option module
▪
No module inserted
▪
Module not permissible in this setup
▪
Module unknown
▪
Module active
Name
... .3
Enter a name (max. 15 characters) for identification.
Fault alarm output
... .4
Determines the signal for the fault alarm output:
'High' stands for >21 mA, 'Low' for <3.6 mA.
▪
High
▪
Low (default)
Error message E1
... .5
Determines whether an error message is issued in case of
condensed state (E1) (see page 84).
▪
No
▪
Yes (default)
Error message E2
... .6
Determines whether an error message is issued in case of
condensed state (E2) (see page 84).
▪
No (default)
▪
Yes
Error message E3
... .7
Determines whether an error message is issued in case of
condensed state (E3) (see page 84).
▪
No (default)
▪
Yes
Assignment of analog
output
... .8
Assignment of a measured value for the analog output (in
filling level mode)
▪
Filling level
▪
Tank pressure (pressure sensor), only when pressure sensor
exists