Operation of Media 7 Differential Pressure Meter
.
Δp
0
= 0,0 % = 4 mA
Δp
100
= 100 % = 20 mA
~
–
+
–
+
Precision regulator with Class 0.1
pressure gauge
Supply unit
mA reading
Supply air reducing
station with oil filter
and test pressure
gauge
Test pressure
Fig. 18:
Test setup
Checking the measuring range (span)
1. Press key (in start screen) to go to the main menu.
2. Select Start-up (1) with or
key and confirm with
key.
3. Select Span (1.6) with or
key and confirm with
key.
The current values for differential pressure, span and maximum differential pressure
(Δp
100
) are displayed.
4.
Use a precision regulator to apply a test pressure corresponding to the max. differen
-
tial pressure Δp
100
while monitoring the pressure gauge.
Î
Set points: Δp = 0 mbar or 4 mA (read note on gas column correction)
Î
When the reading and output signal do not match the indicated Δ p
100
value, readjust
the upper range value (span).