![Samson Media 7 Скачать руководство пользователя страница 70](http://html.mh-extra.com/html/samson/media-7/media-7_mounting-and-operating-instructions_805914070.webp)
70
EB 9510 EN
Malfunctions
Error ID
Message
Possible causes and recommended action
204
AMR temperature sensor
The temperature sensor has failed.
Î
Reset error message. Contact SAMSON's
After-sales Service when this error reoccurs.
205
Temperature inside device below min.
limit
The temperature limit inside the device has fallen
below the adjusted min. limit.
Î
Check whether the heating functions properly
and the heating control is switched on.
Î
Select lower temperature limit.
206
Temperature inside device above max.
limit
The temperature limit inside the device has
exceeded the adjusted max. limit.
Î
Check whether the heating functions properly
and the heating control is switched on.
Î
Select a better location to mount the Media 7
device, if necessary.
207
Large differential pressure drop
The bypass valve has been opened. A
diaphragm rupture in the dp cell exists. The dp
cell leaks.
Î
Check all screw fittings.
301
Power supply unit not recognized
The current firmware of the device does not
support the supply voltage. A firmware update is
necessary.
Î
Contact SAMSON's After-sales Service.
302
Option not recognized
The current firmware of the device does not
support the option. A firmware update is
necessary. The option is defective.
Î
Contact SAMSON's After-sales Service.
303
Option module combination invalid
Option modules are inserted incorrectly or the
incorrect combination of modules has been used.
Î
Check the combination and how the option
modules are inserted.