11-2
EB 9510 EN
Decommissioning
Risk of burn injuries due to hot or cold com-
ponents and pipelines.
Î
Prior to performing any work on the
differential pressure meter, allow
components and pipelines to cool down
or warm up to the ambient temperature.
Î
Wear protective clothing and safety
gloves.
To decommission the differential pressure
meter before removing it, proceed as fol-
lows:
1. Isolate measuring lines.
Î
When a valve block is used:
2. Close the shut-off valves.
3.
Open the equalizing valve.
4. Slowly open the screw of the test con-
nection to release the pressure.
5. Disconnect the power supply.
6. Open the housing cover of the differen-
tial pressure meter and disconnect the
wires for the power supply.