EB 9511 EN
16-5
Annex A (configuration instructions)
Menu
Adjustment range/values/description
Limit 3
... .20
Activate/deactivate limit 3
▪
ON (default), OFF
Mode
... .21
An upper limit can be determined with 'Max. contact' and a
lower limit with 'Min. contact' for limit 3.
▪
Max. contact, Min. contact (default)
Limit
... .22
Setting of limit 3 (depends on selected unit)
▪
0.0 to 100.0 (default: 90.0)
Parameter only shown when 'Signal source' = 'Pressure' or
'Temperature'.
Limit
... .23
Setting of limit 3 (depends on selected unit)
▪
0.0 to 100.0 (default: 90.0)
Parameter only shown when 'Signal source' = 'Unknown' or
'Filling level'.
4 to 20 mA measured
value
... .24
Reading of the current (in mA) at the option module
Relative measured value
... .25
Reading of the current (in %) at the option module
Start test
... .26
Executable function to test a signal reading in the device and
over the web portal. The input signal of the option module is
replaced by an internal test signal and issued by the GSM
module.
Test mode
... .27
Test mode reading: 'Active' while the test is in progress (test du-
ration: 30 s).
▪
Not active (default), Active
Analog input test signal
... .28
Test signals (depending on the selected unit) based on the 4 to
20 mA signal range.
▪
–214748364.7 to 214748364.7 (default: 0)
Содержание 5007-2 Series
Страница 8: ...1 4 EB 9511 EN...
Страница 12: ...2 4 EB 9511 EN...
Страница 24: ...3 12 EB 9511 EN...
Страница 29: ...EB 9510 EN 5 3 Cover Option module Fig 5 1 Inserting option modules...
Страница 36: ...5 10 EB 9510 EN...
Страница 50: ...11 2 EB 9511 EN...
Страница 52: ...12 2 EB 9511 EN...
Страница 54: ...13 2 EB 9511 EN...
Страница 56: ...14 2 EB 9511 EN...
Страница 68: ...17 2 EB 9511 EN...
Страница 69: ......
Страница 70: ...4 EB 9511 EN...
Страница 71: ...EB 9511 EN 5...