3-8
EB 9511 EN
Design and principle of operation
Communication
Local
SAMSON SSP interface and serial interface adapter, TROVIS-VIEW
Remote data transmission
GSM module
Weight
Device (with 4 option modules)
Approx. 1400 g
1)
Impaired operation and readability may arise outside the temperature range.
Measurement is not influenced in the range between –40 and +70 °C.
Table 3-2:
Power supply
24 V version
Input voltage
24 to 36 V DC
Output voltage
12 V DC
Power
24 W
Version
Reverse polarity protection
230 V version
Input voltage
100 to 230 V/50 Hz · 100 to 110 V/60 Hz
Output voltage
14 V DC
Power
Max. 10 W
Table 3-3:
Optional additional functions
AI: Analog input
Version
4 to 20 mA current input, externally powered, galvanically isolated, reverse polarity
protection
Load impedance
≤5.0 V external (corresponding to ≤200 Ω at 20 mA)
Measuring range
0.1 to 21.6 mA
Accuracy
≤1.0 %
Resolution
20 µA
Effect of temperature
0.3 %/10 K
Static destruction limit
38 V DC · 30 V AC
AIA: Analog input active
Version
4 to 20 mA current input, internally powered, reverse polarity protection
Load impedance
≤1 V internal (corresponds to ≤50 Ω at 20 mA)
Output voltage at the
terminal
≥12 VDC to power external two-wire devices
Measuring range
0.1 to 21.6 mA
Содержание 5007-2 Series
Страница 8: ...1 4 EB 9511 EN...
Страница 12: ...2 4 EB 9511 EN...
Страница 24: ...3 12 EB 9511 EN...
Страница 29: ...EB 9510 EN 5 3 Cover Option module Fig 5 1 Inserting option modules...
Страница 36: ...5 10 EB 9510 EN...
Страница 50: ...11 2 EB 9511 EN...
Страница 52: ...12 2 EB 9511 EN...
Страница 54: ...13 2 EB 9511 EN...
Страница 56: ...14 2 EB 9511 EN...
Страница 68: ...17 2 EB 9511 EN...
Страница 69: ......
Страница 70: ...4 EB 9511 EN...
Страница 71: ...EB 9511 EN 5...